Mitsubishi Heavy Industries Air Conditioners

110 fault codes documented

01

Power source faulty — RUN LED OFF, TIMER LED flashes 1 time

The unit detects a faulty power source or improper wiring of power/signal lines. This occurs if communication signals are not detected within 10 seconds after power-on.

05

Wired remote control wiring error — RUN LED OFF, TIMER LED flashes 5 times

The system cannot receive signals from the wired remote control for 35 seconds. This indicates a problem with the remote control wiring, the remote control unit, or the indoor PCB.

35

Cooling high pressure control activated — RUN LED flashes 3 times, TIMER LED flashes 5 times

The system's high-pressure control has activated during cooling operation and caused the compressor to stop. This indicates issues with refrigerant levels, closed service valves, or inefficient heat exchange.

36

Outdoor heat exchanger sensor wire disconnected — RUN LED flashes 3 times, TIMER LED flashes 6 times

The system detects that the outdoor heat exchanger sensor wire is disconnected. This prevents the unit from accurately monitoring temperatures and can lead to incorrect operation.

37

Outdoor heat exchanger sensor abnormal — RUN LED flashes 3 times, TIMER LED flashes 7 times

The outdoor heat exchanger sensor is reporting abnormal readings, such as –55°C or lower (or higher) repeatedly, which affects the unit's ability to operate correctly.

38

Outdoor air temperature sensor abnormal — RUN LED flashes 3 times, TIMER LED flashes 8 times

The outdoor air temperature sensor is reporting abnormal readings, such as –55°C or lower (or higher) continuously, which impacts the unit's control and efficiency.

39

Discharge pipe sensor abnormal — RUN LED flashes 3 times, TIMER LED flashes 9 times

The discharge pipe sensor is reporting abnormal readings (its value exceeds the set limit) or its wire is disconnected, leading to an anomalous stop of the unit.

42

Compressor overheat (110°C) — RUN LED flashes 4 times, TIMER LED flashes 2 times

The compressor has overheated to 110°C, triggering a protective shutdown. This usually indicates an issue with the refrigerant flow, the electronic expansion valve, or the compressor itself.

48

Outdoor unit fan motor abnormal — RUN LED flashes 4 times, TIMER LED flashes 8 times

The outdoor unit's fan motor is detected to be running at 75 min-1 or lower for 30 seconds or longer, indicating a malfunction or obstruction preventing proper fan operation.

51

Current cut error — RUN LED flashes 5 times, TIMER LED flashes 1 time

The compressor has stopped due to a 'current cut', potentially after failing to start multiple times in succession. This suggests problems with compressor wiring, the power transistor, or the compressor itself.

59

Voltage drop / Low speed protective control — RUN LED flashes 5 times, TIMER LED flashes 9 times

The unit detected a voltage drop during operation or the compressor command speed was lower than 32 rps for 60 minutes, leading to the activation of protective control.

60

Rotor lock — RUN LED flashes 6 times, TIMER LED OFF

The compressor rotor has locked after starting, causing the compressor to stop. This indicates a mechanical issue with the compressor itself.

61

Connection lines between indoor and outdoor units faulty — RUN LED flashes 6 times, TIMER LED flashes 1 time

Faulty connection lines between the indoor and outdoor units are detected. This can lead to communication errors or improper operation of the system.

62

Serial transmission error — RUN LED flashes 6 times, TIMER LED flashes 2 times

A serial transmission error is detected, meaning communication signals between units are not correctly detected for 7 minutes and 35 seconds. This is a critical communication fault.

80

Indoor unit fan motor abnormal — RUN LED flashes 8 times, TIMER LED OFF

The indoor unit's fan motor is detected to be running at 300 min-1 or lower speed while the air conditioner is operating and the fan motor is commanded to be ON.

82

Indoor heat exchanger sensor abnormal — RUN LED flashes 8 times, TIMER LED flashes 2 times

The indoor heat exchanger sensor is reporting abnormal readings, its wire is disconnected, broken, or short-circuited, leading to an anomalous stop of the unit.

84

Drain trouble — RUN LED flashes 8 times, TIMER LED flashes 4 times

There is an issue with the condensate drain system, detected by the float switch being open continuously for 3 seconds or a disconnected float switch connector/wire.

85

Anti-frost control activated — RUN LED flashes 8 times, TIMER LED flashes 5 times

The anti-frost control has activated, causing the compressor to stop during cooling operation. This is often a normal protective function when the outdoor temperature drops very low (e.g., –28°C or lower for 40 minutes during heating operation).

86

Anti-condensation control activated — RUN LED flashes 8 times, TIMER LED flashes 6 times

The anti-condensation prevention control is operating. This typically occurs in conditions of high humidity to prevent moisture buildup inside the unit or ductwork.

87

Heating high pressure control activated — RUN LED flashes 8 times, TIMER LED flashes 7 times

The system's high-pressure control has activated during heating operation and caused the compressor to stop. This indicates issues with refrigerant levels, closed service valves, or inefficient heat exchange during heating.

E1 / 3 Red Flashes

E1 / 3 Red Flashes - Remote control communication error

The remote control displays E1, and the indoor unit's red LED flashes three times (while the green LED keeps flashing). This indicates a problem with the remote control communication circuit.

E1 / Indoor Red LED 3 flashes

Error E1 / Indoor Red LED Flashes 3 times — Remote controller wiring open circuit

Error code E1, indicated by the indoor unit's red LED flashing three times, means there is an open circuit in the remote controller's wiring. This prevents proper communication.

E2 / Indoor Red LED 1 flash

Error E2 / Indoor Red LED Flashes once — Indoor unit address duplication or too many units

Error E2, shown by a single flash of the indoor unit's red LED, indicates that an indoor unit's address is duplicated or more than 49 indoor units are connected to the network, which exceeds the maximum limit.

E3 / Indoor & Outdoor Red LEDs 2 flashes

Error E3 / Indoor and Outdoor Red LEDs Flashes Twice — Outdoor/Indoor communication error

When both the indoor and outdoor unit's red LEDs flash twice, it signals a communication error between the outdoor and indoor units. This prevents the system from operating correctly.

E3 / Indoor Red LED 2 flashes

Error E3 / Indoor Red LED Flashes Twice — Incorrect outdoor unit address setting

Error E3, indicated by the indoor unit's red LED flashing twice, means the outdoor unit's address setting is incorrect. Proper addressing is essential for system communication.

E3 / Indoor Red LED 2 flashes (Outdoor Red LED Off)

Error E3 / Indoor Red LED Flashes Twice — Outdoor unit PCB or inverter fault

Error E3, with the indoor unit's red LED flashing twice and the outdoor unit's red LED staying off, suggests a failure in the outdoor unit's control PCB or faulty inverter components.

E5

Error E5 and Indoor Red LED flashes 2 times — Communication error during operation

Normal communication between the indoor and outdoor units has been interrupted for more than 2 minutes while the unit is operating. This could be due to issues with wiring or temporary electrical noise.

E5 / 2 Red Flashes

E5 / 2 Red Flashes - Communication error during operation

The remote control displays E5, and the indoor unit's red LED flashes twice (while the green LED keeps flashing). This indicates a communication error between the indoor and outdoor units during operation.

E5 / Indoor Red LED 2 flashes

Error E5 / Indoor Red LED Flashes Twice — Outdoor unit microcomputer failure

Error E5, shown by the indoor unit's red LED flashing twice, indicates a failure in the outdoor unit's microcomputer. This critical component manages the outdoor unit's operations.

E6 / 1 Red Flash

E6 / 1 Red Flash - Indoor heat exchanger temperature sensor anomaly

The remote control displays E6, and the indoor unit's red LED flashes once (while the green LED keeps flashing). This indicates an issue with the indoor heat exchanger temperature sensor.

E6 / Indoor Red LED 1 flash

Error E6 / Indoor Red LED Flashes Once — Indoor heat exchanger sensor fault

Error E6, indicated by a single flash of the indoor unit's red LED, means the indoor unit's heat exchanger sensor (ThIR) is defective, either due to an open or closed circuit, or has a poor connection to the indoor PCB.

E7 / 1 Red Flash

E7 / 1 Red Flash - Return air temperature sensor anomaly

The remote control displays E7, and the indoor unit's red LED flashes once (while the green LED keeps flashing). This indicates an issue with the indoor return air temperature sensor.

E7 / Indoor Red LED 1 flash

Error E7 / Indoor Red LED Flashes Once — Indoor return air sensor fault or heating overload

Error E7, signaled by a single flash of the indoor unit's red LED, indicates a defective indoor return air sensor (ThIA) or a poor connection. It can also be triggered by an unusually high temperature in the indoor heat exchanger during heating, suggesting an overload.

E8 / 1 Red Flash

E8 / 1 Red Flash - Heating overload operation

The remote control displays E8, and the indoor unit's red LED flashes once (while the green LED keeps flashing). This indicates the unit is experiencing an overload during heating operation, leading to abnormally high indoor heat exchanger temperatures.

E8 / Indoor Red LED 1 flash

Error E8 / Indoor Red LED Flashes Once — Indoor unit sensor, drain, or float switch fault

Error E8, indicated by one flash of the indoor unit's red LED, can point to several issues: a closed circuit in the indoor heat exchanger sensor (ThIR), a fault with the drain motor (DM), condensate remaining in the drain tray due to blockage, or a float switch stuck in a high position.

E9 / 1 Red Flash

E9 / 1 Red Flash - Drain trouble

The remote control displays E9, and the indoor unit's red LED flashes once (while the green LED keeps flashing). This indicates a problem with the unit's drainage system.

E9 / Indoor Red LED 1 flash

Error E9 / Indoor Red LED Flashes Once — Indoor PCB float switch or drain motor circuit fault

Error E9, indicated by a single flash of the indoor unit's red LED, means there's a defective input circuit for the float switch or a defective output circuit for the drain motor on the indoor PCB.

E10

E10 - Excessive number of connected indoor units

The remote control displays E10. This indicates that more than 17 indoor units are being controlled by a single remote control in a multi-unit setup, exceeding the system's limit.

E11

Error E11 — Address setting error of indoor units

This error occurs when the indoor unit address was incorrectly set using the 'Master IU address set' function on the remote control. Addresses for this system should be set directly via DIP switches on the indoor unit PCB.

E11 / Red LED Keeps Flashing

E11 / Red LED Keeps Flashing - Indoor unit address setting error

The remote control displays E11, and the indoor unit's red and green LEDs both keep flashing. This indicates an error in the address settings of the indoor units.

E12 / Indoor Red LED 1 flash

Error E12 / Indoor Red LED Flashes Once — Addressing error (factory settings or auto address)

Error E12, indicated by a single flash of the indoor unit's red LED, signals an addressing issue. This can happen if units retain factory addresses (48 or 49), if a unit isn't set to 49 during auto-addressing, or if auto-addressing isn't compatible with the system type (only single KX2 systems).

E14 / Indoor Red LED 3 flashes

Error E14 / Indoor Red LED Flashes 3 times — Master/slave system setup or wiring error

Error E14, indicated by three flashes of the indoor unit's red LED, points to problems in a master/slave system setup. This could be incorrect SW5 settings on the indoor PCB, wrong control wiring (XYZ), or an open circuit in the control wiring between units.

E16

Error E16 — Faulty indoor fan motor (normal LED status)

Error E16 indicates a faulty indoor fan motor. The system's LEDs may appear in their normal operational state, making the fault harder to diagnose without the error code.

E16 / 1(2) Red Flashes

E16 / 1 or 2 Red Flashes - Indoor fan motor anomaly

The remote control displays E16, and the indoor unit's red LED flashes once or twice (while the green LED keeps flashing). This indicates an issue with the indoor fan motor.

E16 / Indoor Red LED 1 flash

Error E16 / Indoor Red LED Flashes once — Faulty indoor fan motor

Error E16, indicated by a single flash of the indoor unit's red LED, means there is a faulty indoor fan motor. This prevents proper airflow and system operation.

E19 / 1 Red Flash

E19 / 1 Red Flash - Improper operation mode setting

The remote control displays E19, and the indoor unit's red LED flashes once (while the green LED keeps flashing). This indicates an improper operation mode setting within the indoor unit's control PCB.

E20 / 1(2) Red Flashes

E20 / 1 or 2 Red Flashes - Indoor fan motor rotation speed anomaly

The remote control displays E20, and the indoor unit's red LED flashes once or twice (while the green LED keeps flashing). This indicates an anomaly with the indoor fan motor's rotation speed.

E28

E28 - Remote control temperature sensor anomaly

The remote control displays E28 (while the indoor unit's green LED keeps flashing and red LED stays off). This indicates a problem with the remote control's temperature sensor.

E30 / Outdoor Red LED 1 flash

Error E30 / Outdoor Red LED Flashes once — Indoor/outdoor unit connection error

Error E30, indicated by a single flash of the outdoor unit's red LED, means there is a connection error between the indoor and outdoor units. This prevents proper system operation.

E31 / Outdoor Red LED 1 flash

Error E31 / Outdoor Red LED Flashes Once — Indoor or outdoor unit addressing error

Error E31, indicated by one flash of the outdoor unit's red LED, points to an addressing problem. This can be a duplicated indoor unit address (U00-U47) or an incorrect setting for the outdoor unit's address.

E32 / Outdoor Red LED 1 flash

Error E32 / Outdoor Red LED Flashes Once — Mains power phase error

Error E32, indicated by a single flash of the outdoor unit's red LED, signals an issue with the mains power phasing. This means two phases might need to be swapped, or the L2 phase has been detected as open.

E34 / Outdoor Red LED 1 flash

Error E34 / Outdoor Red LED Flashes Once — Low current or open phase on L3

Error E34, shown by one flash of the outdoor unit's red LED, indicates an abnormally low current or no current detected on the L3 phase, or an open phase on L3 (secondary side of the contactor).

E35 / Outdoor Red LED 1 flash

Error E35 / Outdoor Red LED Flashes Once — Outdoor heat exchanger sensor fault or cooling high pressure

Error E35, signaled by a single flash of the outdoor unit's red LED, means the outdoor unit's heat exchanger sensor (ThOR) is defective (open or closed circuit), has a poor connection, or indicates excessively high pressure during cooling.

E35 / Remote Keeps Flashing

E35 / Remote Control Keeps Flashing - Cooling overload operation

The remote control keeps flashing (while the indoor unit's green LED keeps flashing and red LED stays off). This indicates the outdoor unit is experiencing an overload during cooling operation, specifically a higher outdoor heat exchanger temperature.

E36

E36 - Discharge pipe temperature error

The remote control displays E36 (while the indoor unit's green LED keeps flashing and red LED stays off). This indicates an error with the discharge pipe temperature, likely due to abnormally high temperatures.

E36 / Outdoor Red LED 1 flash

Error E36 / Outdoor Red LED Flashes Once — Abnormally high discharge temperature

Error E36, shown by a single flash of the outdoor unit's red LED, indicates an abnormally high discharge temperature. This can be caused by insufficient refrigerant or a defective compressor discharge temperature sensor (ThOD).

E37

E37 - Outdoor heat exchanger temperature sensor anomaly

The remote control displays E37 (while the indoor unit's green LED keeps flashing and red LED stays off). This indicates a problem with the outdoor heat exchanger temperature sensor.

E37 / Outdoor Red LED 1 flash

Error E37 / Outdoor Red LED Flashes Once — Outdoor heat exchanger sensor fault (general)

Error E37, indicated by one flash of the outdoor unit's red LED, signifies a general fault with an outdoor unit heat exchanger sensor (ThOR). This could be due to a defective sensor or a poor connection.

E37-1 / Outdoor Red LED 1 flash

Error E37-1 / Outdoor Red LED Flashes Once — Outdoor heat exchanger thermistor Tho-R1 failure

Error E37-1, identified by one flash of the outdoor unit's red LED, indicates a failure of the outdoor heat exchanger thermistor Tho-R1. This sensor is crucial for temperature readings.

E37-2 / Outdoor Red LED 2 flashes

Error E37-2 / Outdoor Red LED Flashes Twice — Outdoor heat exchanger thermistor Tho-R2 failure

Error E37-2, identified by two flashes of the outdoor unit's red LED, indicates a failure of the outdoor heat exchanger thermistor Tho-R2. This sensor is crucial for temperature readings.

E37-3 / Outdoor Red LED 3 flashes

Error E37-3 / Outdoor Red LED Flashes 3 times — Outdoor heat exchanger thermistor Tho-R3 failure

Error E37-3, identified by three flashes of the outdoor unit's red LED, indicates a failure of the outdoor heat exchanger thermistor Tho-R3. This sensor is crucial for temperature readings.

E37-4 / Outdoor Red LED 4 flashes

Error E37-4 / Outdoor Red LED Flashes 4 times — Outdoor heat exchanger thermistor Tho-R4 failure

Error E37-4, identified by four flashes of the outdoor unit's red LED, indicates a failure of the outdoor heat exchanger thermistor Tho-R4. This sensor is crucial for temperature readings.

E37-5 / Outdoor Red LED 5 flashes

Error E37-5 / Outdoor Red LED Flashes 5 times — Outdoor heat exchanger thermistor Tho-SC failure

Error E37-5, identified by five flashes of the outdoor unit's red LED, indicates a failure of the outdoor heat exchanger thermistor Tho-SC. This sensor is crucial for temperature readings.

E37-6 / Outdoor Red LED 6 flashes

Error E37-6 / Outdoor Red LED Flashes 6 times — Outdoor heat exchanger thermistor Tho-H failure

Error E37-6, identified by six flashes of the outdoor unit's red LED, indicates a failure of the outdoor heat exchanger thermistor Tho-H. This sensor is crucial for temperature readings.

E38

E38 - Outdoor air temperature sensor anomaly

The remote control displays E38 (while the indoor unit's green LED keeps flashing and red LED stays off). This indicates a problem with the outdoor air temperature sensor.

E38 / Outdoor Red LED 1 flash

Error E38 / Outdoor Red LED Flashes Once — Outside air temperature sensor fault

Error E38, indicated by one flash of the outdoor unit's red LED, means the outside air temperature sensor (ThoA) is defective (open circuit) or has a poor connection to the outdoor unit PCB.

E39

E39 - Discharge pipe temperature sensor anomaly

The remote control displays E39 (while the indoor unit's green LED keeps flashing and red LED stays off). This indicates a problem with the discharge pipe temperature sensor.

E39 / Outdoor Red LED 1 flash

Error E39 / Outdoor Red LED Flashes Once — Compressor discharge temperature sensor fault

Error E39, indicated by one flash of the outdoor unit's red LED, means the compressor discharge temperature sensor (ThOD) is defective (open circuit) or has a poor connection to the outdoor unit PCB.

E40

E40 - Service valve (gas side) closing operation

The remote control displays E40 (while the indoor unit's green LED keeps flashing and red LED stays off). This indicates that the service valve on the gas side is closed.

E40 / Outdoor Red LED 1 flash

Error E40 / Outdoor Red LED Flashes Once — High-pressure switch tripped

Error E40, signaled by one flash of the outdoor unit's red LED, means the high-pressure switch (63H or 63H1) has tripped. This can be due to system overcharging with refrigerant, a shut service valve, or insufficient airflow over the condenser coil.

E41 / Outdoor Red LED 1 flash

Error E41 / Outdoor Red LED Flashes Once — Inverter power transistor overheated

Error E41, indicated by one flash of the outdoor unit's red LED, means the power transistor for the inverter has overheated. This can damage the inverter and disrupt system operation.

E42

E42 - Current cut / Compressor over-current

The remote control displays E42 (while the indoor unit's green LED keeps flashing and red LED stays off). This indicates a 'current cut' event, likely due to anomalous compressor over-current or a service valve closing operation.

E42 / Outdoor Red LED 1 flash

Error E42 / Outdoor Red LED Flashes Once — Abnormally high current in compressor

Error E42, indicated by one flash of the outdoor unit's red LED, means an abnormally high current has been detected in the compressor. This is a serious electrical fault that can damage the compressor.

E43 / Outdoor Red LED 1 flash

Error E43 / Outdoor Red LED Flashes Once — Max indoor units exceeded

Error E43, indicated by one flash of the outdoor unit's red LED, means the maximum allowed number of indoor units connected to a single outdoor unit has been exceeded.

E45 / Outdoor Red LED 1 flash

Error E45 / Outdoor Red LED Flashes Once — Inverter and outdoor PCB transmission error

Error E45, shown by one flash of the outdoor unit's red LED, indicates a transmission error between the inverter and the outdoor unit PCB. This could be due to a loose connection of the CnI cable.

E46

Error E46 — Conflict of address settings

Error E46 indicates a conflict in address settings within the system. This can occur if automatic, manual, and remote control addresses are mixed on a single network, causing confusion for the system.

E47

E47 - Active filter voltage error

The remote control displays E47 (while the indoor unit's green LED keeps flashing and red LED stays off). This indicates an error related to the active filter voltage on the outdoor unit control PCB.

E47 / 47

Error E47 or RUN LED flashes 4 times, TIMER LED flashes 7 times — Active filter voltage error (or Red LED flashes 1 time for overvoltage)

The converter voltage has exceeded the target voltage (3 times within 20 minutes) or fallen below DC210V (1 time within 5 seconds after power ON). If overvoltage (DC higher than 400V) occurs, the Indoor Red LED will flash once.

E47 / Outdoor Red LED 1 flash

Error E47 / Outdoor Red LED Flashes Once — Inverter over voltage

Error E47, indicated by one flash of the outdoor unit's red LED, means the inverter has detected an over-voltage condition. This can be caused by unstable power supply.

E48

E48 - Outdoor fan motor anomaly

The remote control displays E48 (while the indoor unit's green LED keeps flashing and red LED stays off). This indicates an anomaly with the outdoor fan motor rotation. The system stops if the fan speed drops below 75 min⁻¹ for 30 seconds, and may restart after 3 minutes. If this anomaly occurs 3 times within 60 minutes after the initial detection, the error is permanent.

E48 / Outdoor Red LED 1 flash

Error E48 / Outdoor Red LED Flashes Once — DC Outdoor Fan motor fault

Error E48, indicated by one flash of the outdoor unit's red LED, signals a fault with the DC outdoor fan motor. This fan is crucial for heat exchange in the outdoor unit.

E49 / Outdoor Red LED 1 flash

Error E49 / Outdoor Red LED Flashes Once — Low pressure, low voltage, or Inverter PCB fault

Error E49, indicated by one flash of the outdoor unit's red LED, signals either a low pressure fault, low voltage detected in the system, or a fault with the inverter PCB. All these can prevent proper operation.

E51

Error E51 — Power transistor anomaly (SRC50, 60 models)

The power transistor primary current has exceeded its safe limit for 3 seconds, causing the compressor to stop. This indicates a problem with the power transistor assembly on the outdoor unit.

E51 / Outdoor Red LED 1 or 2 flashes

Error E51 / Outdoor Red LED Flashes Once or Twice — Power transistor overheat

Error E51, shown by one or two flashes of the outdoor unit's red LED, means the power transistor has overheated. This component is part of the inverter circuit and overheating can lead to system shutdown.

E53 / Outdoor Red LED 1 flash

Error E53 / Outdoor Red LED Flashes Once — Suction pipe thermistor or low pressure sensor fault

Error E53, indicated by one flash of the outdoor unit's red LED, points to a disconnected suction pipe thermistor (Tho-S) or a disconnected/output error with the low pressure sensor (PSL). Both are critical for system monitoring.

E54 / Outdoor Red LED 2 flashes

Error E54 / Outdoor Red LED Flashes Twice — Pressure sensor error

Error E54, indicated by two flashes of the outdoor unit's red LED, points to a general pressure sensor issue. This could be related to either low or high pressure sensors.

E54-1 / Outdoor Red LED 1 flash

Error E54-1 / Outdoor Red LED Flashes Once — Low pressure sensor (PSL) disconnection/output error

Error E54-1, indicated by one flash of the outdoor unit's red LED, signifies a disconnection or output error from the low pressure sensor (PSL). This sensor monitors system pressure.

E54-2 / Outdoor Red LED 2 flashes

Error E54-2 / Outdoor Red LED Flashes Twice — High pressure sensor (PSH) disconnection/output error

Error E54-2, indicated by two flashes of the outdoor unit's red LED, signifies a disconnection or output error from the high pressure sensor (PSH). This sensor monitors system pressure.

E55 / Outdoor Red LED 1 flash

Error E55 / Outdoor Red LED Flashes Once — Compressor under dome thermistor disconnected

Error E55, indicated by one flash of the outdoor unit's red LED, means the compressor under dome thermistor is disconnected. This sensor monitors the compressor's temperature for safe operation.

E56 / Outdoor Red LED 1 flash

Error E56 / Outdoor Red LED Flashes Once — Power transistor thermistor faulty or disconnected

Error E56, indicated by one flash of the outdoor unit's red LED, means the power transistor thermistor is either faulty or disconnected (specifically for FDCVA151-251 models). This sensor monitors power transistor temperature.

E57

E57 - Insufficient refrigerant or service valve closed

The remote control displays E57 (while the indoor unit's green LED keeps flashing and red LED stays off). This indicates either an insufficient amount of refrigerant in the system or that a service valve is closed.

E57 / Outdoor Red LED 1 flash

Error E57 / Outdoor Red LED Flashes Once — Refrigerant leak or shortage

Error E57, indicated by one flash of the outdoor unit's red LED, means there is a refrigerant leak or a shortage of refrigerant in the system (specifically for FDCVA151-251 models).

E58

E58 - Current safe stop / Overload protection

The remote control displays E58 (while the indoor unit's green LED keeps flashing and red LED stays off). This indicates a 'current safe stop' due to overload operation, overcharge, or compressor locking. The system has stopped to protect itself.

E58 / 58

Error E58 or RUN LED flashes 5 times, TIMER LED flashes 8 times — Current safe stop (SRC50, 60 models) or Outdoor Red LED 3 times

The system initiated a 'current safe stop' during operation, specifically when the compressor speed was 30 rps or under. This suggests problems with refrigerant levels, airflow, or key sensors.

E59

E59 - Compressor startup failure

The remote control displays E59 (while the indoor unit's green LED keeps flashing and red LED stays off). This indicates a failure of the compressor to start properly.

E59 / Outdoor Red LED 1 to 5 flashes

Error E59 / Outdoor Red LED Flashes 1 to 5 times — Compressor start-up error

Error E59, indicated by 1 to 5 flashes of the outdoor unit's red LED, means there's an error during the compressor start-up sequence. This can prevent the unit from heating or cooling.

E60

E60 - Compressor rotor lock error

The remote control displays E60 (while the indoor unit's green LED stays off and red LED keeps flashing). This indicates a compressor rotor lock error, meaning the compressor's rotor is unable to rotate. The system attempts to detect rotor position, and if it fails again, the compressor stops.

E60 / Outdoor Red LED 1 or 2 flashes

Error E60 / Outdoor Red LED Flashes Once or Twice — Compressor position detection error

Error E60, shown by one or two flashes of the outdoor unit's red LED, means there's a compressor position detection error. This sensor helps the system understand the compressor's rotation.

E63 / Outdoor Red LED 1 flash

Error E63 / Outdoor Red LED Flashes Once — Emergency stop of indoor unit

Error E63, indicated by one flash of the outdoor unit's red LED, means an emergency stop has been activated for an indoor unit. This could be due to a safety mechanism or system malfunction.

Earth leakage breaker activated

Earth Leakage Breaker Activated - Electrical trip

The earth leakage breaker has tripped, cutting power to the unit. This often occurs due to low insulation resistance in the compressor or an improper breaker type for inverter units.

Indoor Green LED Off or On continuously

Indoor Green LED Off or On continuously — Indoor circuit board or CPU failure

The indoor unit's green LED is either continuously off or continuously on, suggesting a problem with the indoor unit's circuit board or central processing unit (CPU).

Indoor Red LED 2 flashes

Indoor Red LED Flashes Twice — No mains power at outdoor unit

The indoor unit's red LED flashes twice, signaling that there is no mains power reaching the outdoor unit. This could be due to the power being off or a power failure.

Indoor Red/Green LEDs Off or On continuously

Indoor Red and Green LEDs Off or On continuously — Indoor circuit board or CPU failure

Both the red and green LEDs on the indoor unit are either continuously off or continuously on. This pattern points to a failure of the indoor unit's circuit board or its central processing unit (CPU).

LCD Flashes continuously or Off / Outdoor Red LED Flashes Twice

LCD Flashes continuously or Off and Outdoor Red LED Flashes Twice — Indoor/outdoor wiring error

The LCD display on the remote controller continuously flashes or is off, and the outdoor unit's red LED flashes twice. This indicates an open circuit or poor connection in the interconnecting wiring between the indoor and outdoor units.

No indication

No indication — No mains power

The unit has no LED indication because it is not receiving mains power. This could be due to a power outage or a broken L phase wire.

No-indication (Remote), Red LED OFF, Green LED OFF

Remote Control No Display, Indoor Unit LEDs Off - Power source issue

The remote control shows no display, and both the red and green LEDs on the indoor unit are off. This indicates a problem with the indoor unit's power source.

Outdoor Red LED 3 flashes

Outdoor Red LED Flashes 3 times — Remote controller wiring fault

The outdoor unit's red LED flashes three times, indicating an issue with the remote controller wiring. This can be caused by reversed connections or a broken wire.

Red LED Keeps Flashing, Green LED Stays OFF (Option Control)

Red LED Keeps Flashing, Green LED Off - Communication error (option control in-use)

The indoor unit's red LED keeps flashing and the green LED stays off. This indicates a communication error within an optional control unit, such as SC-SL2NA-E or SC-SL4-AE/BE.

WAIT

Remote control displays "WAIT" and Indoor Red LED keeps flashing — Communication error at initial operation

The system is detecting a communication error when first powered on. This message may appear if the main power breaker is repeatedly turned on and off too quickly.

WAIT / INSPECT I/U (Remote)

Remote Control Displays WAIT or INSPECT I/U - Communication or setting error

The remote control displays 'WAIT' or 'INSPECT I/U'. This indicates a general communication error between indoor and outdoor units, or between remote controls, potentially due to wiring issues or incorrect settings.