Mitsubishi Heavy Industries · Air Conditioners
There is an issue with the condensate drain system, detected by the float switch being open continuously for 3 seconds or a disconnected float switch connector/wire.
Click steps to track your progress.
Turn off the main power to the unit.
Check the indoor unit's drain pan for water overflow and clear any visible blockages in the drain hose.
Inspect the float switch for proper operation and ensure its connector and wire are securely attached.
Verify the drain pump (if your unit has one) is functioning correctly and its wires are not broken or loose.
Clean the drain pan and ensure free flow of condensate away from the unit.