48

Outdoor unit fan motor abnormal — RUN LED flashes 4 times, TIMER LED flashes 8 times

Mitsubishi Heavy Industries · Air Conditioners

What does 48 mean?

The outdoor unit's fan motor is detected to be running at 75 min-1 or lower for 30 seconds or longer, indicating a malfunction or obstruction preventing proper fan operation.

Common Causes

  • Faulty outdoor fan motor
  • Poor connector connections to the fan motor
  • Obstruction preventing fan rotation
  • Faulty outdoor PCB

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Turn off the main power to the unit.

  2. 2

    Inspect the outdoor fan motor and fan blades for any obstructions (debris, ice) that might be preventing it from rotating freely and remove them.

  3. 3

    Check the electrical connections to the outdoor fan motor for any looseness or damage.

  4. 4

    Manually check if the fan blade spins freely without power.

  5. 5

    If the fan motor is unobstructed and connections are sound, the outdoor fan motor or outdoor PCB may be faulty and require professional service.

Browse all codes in this manual (110)
Verified technical data. Last updated: April 2026