York Smart Equipment Control

17 fault codes documented

Building Pressure Sensor Failure

Building Pressure Sensor Failure alarm

This alarm occurs when the economizer module recognizes a building pressure input, but then loses that recognition. It can also happen if the pressure readings go outside the sensor's operating range.

C1 Locked Out Due to High Pressure

Refrigeration Circuit 1 High Pressure Lockout

This alarm occurs when 24 VAC power is lost from the HPS1 terminal, indicating a high-pressure condition in refrigeration circuit 1. Multiple occurrences within an hour will cause a hard lockout.

C2 Locked Out Due to High Pressure

Refrigeration Circuit 2 High Pressure Lockout

This alarm occurs when 24 VAC power is lost from the HPS2 terminal, indicating a high-pressure condition in refrigeration circuit 2. Multiple occurrences within an hour will cause a hard lockout.

C3 Locked Out Due to High Pressure

Refrigeration Circuit 3 High Pressure Lockout

This alarm occurs when 24 VAC power is lost from the HPS3 terminal, indicating a high-pressure condition in refrigeration circuit 3. Multiple occurrences within an hour will cause a hard lockout.

Dirty Filter Switch Trip

Dirty Filter Switch Trip alarm

This alarm is activated when the dirty filter switch (DFS) closes, sending a 24 VAC signal to the SEC board. It indicates that the air filters need to be changed.

Econ Economizing When It Should Not

Econ Economizing When It Should Not alarm

This alarm means the economizer damper is open beyond its minimum position when it should not be, typically occurring when the unit is in occupied mode but not in a free cooling situation.

Econ Not Economizing When It Should

Economizer Not Activating When Expected

This alarm means the economizer damper is not operating within its set parameters, and the outside air damper is open less than its minimum setting while the unit is in occupied mode.

Evaporator Coil Temperature 1 Sensor Fail

Evaporator Coil Temperature 1 Sensor Fail alarm

This alarm signifies that the Evaporator Coil 1 (EC1) sensor has failed, either due to an open circuit or by providing readings outside its expected range. This sensor protects the compressor from freezing.

Evaporator Coil Temperature 2 Sensor Fail

Evaporator Coil Temperature 2 Sensor Failure

This alarm indicates a failure with the Evaporator Coil Temperature 2 (EC2) sensor. This sensor is crucial for protecting the compressor from freezing conditions.

Evaporator Coil Temperature 3 Sensor Fail

Evaporator Coil Temperature 3 Sensor Failure

This alarm indicates a failure with the Evaporator Coil Temperature 3 (EC3) sensor, likely due to an open circuit or exceeding its input range. This sensor protects the compressor.

Evaporator Coil Temperature 4 Sensor Fail

Evaporator Coil Temperature 4 Sensor Failure

This alarm indicates a failure with the Evaporator Coil Temperature 4 (EC4) sensor, likely due to an open circuit or exceeding its input range. This sensor protects the compressor.

Excessive Supply Air Temp

Excessive Supply Air Temperature Alarm

This alarm triggers when the supply air temperature exceeds the set heating or cooling limit. This can occur if the Supply Air Heating Limit or Supply Air Cooling Limit is enabled.

HS2 Off Due to Gas Valve

HS2 Off Due to Gas Valve alarm

This alarm indicates that the heating stage 2 (HS2) is disabled because of an issue related to the gas valve. This could be due to a lack of a command signal or a problem with the gas valve system.

HS3 Off Due to Gas Valve

HS3 Off Due to Gas Valve alarm

This alarm means that heating stage 3 (HS3) is deactivated due to an issue with the gas valve. It could be related to the command signal for heating or the gas valve's operational status.

Supply Fan VFD Failure

Supply Fan VFD Failure alarm

This alarm indicates a problem with the variable frequency drive (VFD) that controls the supply fan. It may occur if there is a fault within the VFD itself or if the electrical connection to it is interrupted.

Unit Shutdown Due to Smoke

Unit Shutdown Due to Smoke alarm

This alarm is triggered when the 24 VAC power supply to the SDR input terminal on the SEC board is lost. This input is typically connected to a smoke detector circuit.

Using Return Instead Of Space

Using Return Instead Of Space indicator

This is not an alarm, but an indicator that the system is currently using the return air sensor for temperature readings because it cannot recognize a space indoor temperature sensor.

York Smart Equipment Control Fault Codes — Complete Error List | CodeRegistry