York · Smart Equipment Control
This alarm indicates that the heating stage 2 (HS2) is disabled because of an issue related to the gas valve. This could be due to a lack of a command signal or a problem with the gas valve system.
Click steps to track your progress.
If using a 24 VAC input, check for 24 VAC at the W2 input when a heat command is active. If not using a 24 VAC input, verify the space temperature is below the heating set point.
Check if the H2 output is commanding 24 VAC to the ignition control module. If not, check the 24 VAC for outputs terminal.
If power is not present at H2 or the outputs terminal, trace the wiring for power loss. If power is present, check the ignition control module and gas valve.
Verify the ignition control module is completing its sequence correctly. Check for MV feedback.
If using a 24 VAC input to W2, ensure there is no voltage leak (even 0.5 VAC can cause issues).
If two transformers are installed, verify the LV phasing.