Fujitsu 410A Multi-Zone Mini-Split Systems
60 fault codes documented
6 Times, 4 Times Continuous (64) — Active Filter / PFC Circuit error
This error indicates a problem with the active filter or PFC circuit, often due to high (over 425V) or low (under 80V) inverter input DC voltage, or a brief power cut-off at low voltage.
6 Times, 5 Times Continuous (65) — IPM error / Trip terminal L error
This indicates an Intelligent Power Module (IPM) error, meaning an abnormal current value was detected at the IPM, or heat radiation is blocked.
7 Times, 1 Time Continuous (71) — Discharge thermistor error
This error occurs when the discharge pipe temperature thermistor is detected as open or short-circuited either at power-up or while the compressor is running.
All Branch Box LEDs are lit — Connected combination error.
All five LEDs on the branch box are illuminated, indicating an error related to the combination of connected indoor and outdoor units.
Branch Box LED 401 & 405 are lit — Primary unit identifying display.
LED 401 and LED 405 are lit, indicating the branch box is functioning as the primary unit in a multi-unit setup. This is a normal status.
Four Branch Box LEDs lit, last one unlit — Power frequency error.
Four LEDs on the branch box are lit, but the fifth (LED 405) is unlit, indicating an issue with the power frequency.
Branch Box LED 402 blinks 1 time — EEPROM error.
LED 402 flashes once, indicating an error with the EEPROM (Electronically Erasable Programmable Read-Only Memory) in the branch box.
Branch Box LED 402 blinks 2 times — Model information error.
LED 402 flashes twice, indicating that the model information stored in the branch box is incorrect or corrupted.
Branch Box LED 402 blinks 3 times — Serial communication error (outdoor unit or between branch boxes).
LED 402 flashes three times, indicating a serial communication error either between the outdoor unit and the branch box, or between multiple branch boxes.
Branch Box LED 402 blinks 4 times — Serial communication error between branch boxes.
LED 402 flashes four times, specifically indicating a serial communication problem between different branch boxes in a multi-zone system.
Branch Box LED 402 blinks 5 times — Serial communication error with Indoor Unit A.
LED 402 flashes five times, indicating a serial communication error between the branch box and Indoor Unit A.
Branch Box LED 402 blinks 6 times & LED 403 is lit — Indoor Unit A, liquid pipe thermistor error.
LED 402 flashes six times and LED 403 is lit, indicating an error with the liquid pipe thermistor for Indoor Unit A.
Branch Box LED 402 blinks 6 times & LED 404 is lit — Indoor Unit B, liquid pipe thermistor error.
LED 402 flashes six times and LED 404 is lit, indicating an error with the liquid pipe thermistor for Indoor Unit B.
Branch Box LED 402 blinks 6 times & LED 405 is lit — Indoor Unit C, liquid pipe thermistor error.
LED 402 flashes six times and LED 405 is lit, indicating an error with the liquid pipe thermistor for Indoor Unit C.
Branch Box LED 402 blinks 7 times & LED 403 is lit — Indoor Unit A, gas pipe thermistor error.
LED 402 flashes seven times and LED 403 is lit, indicating an error with the gas pipe thermistor for Indoor Unit A.
Branch Box LED 402 blinks 7 times & LED 404 is lit — Indoor Unit B, gas pipe thermistor error.
LED 402 flashes seven times and LED 404 is lit, indicating an error with the gas pipe thermistor for Indoor Unit B.
Branch Box LED 402 blinks 7 times & LED 405 is lit — Indoor Unit C, gas pipe thermistor error.
LED 402 flashes seven times and LED 405 is lit, indicating an error with the gas pipe thermistor for Indoor Unit C.
Branch Box LED 402 blinks 8 times & LED 403 is lit — Indoor Unit A, EEV control error.
LED 402 flashes eight times and LED 403 is lit, indicating an error with the Electronic Expansion Valve (EEV) control for Indoor Unit A.
Branch Box LED 402 blinks 8 times & LED 404 is lit — Indoor Unit B, EEV control error.
LED 402 flashes eight times and LED 404 is lit, indicating an error with the Electronic Expansion Valve (EEV) control for Indoor Unit B.
Branch Box LED 402 blinks 8 times & LED 405 is lit — Indoor Unit C, EEV control error.
LED 402 flashes eight times and LED 405 is lit, indicating an error with the Electronic Expansion Valve (EEV) control for Indoor Unit C.
Branch Box LED 402 blinks 9 times — Remote controller communication error.
LED 402 flashes nine times, indicating a communication error with the remote controller.
Branch Box LED 402 blinks 1 time — Secondary unit 1 identifying display.
LED 402 flashes once, indicating the branch box is functioning as secondary unit 1 in a multi-unit setup. This is a normal status.
Branch Box LED 402 blinks 2 times — Secondary unit 2 identifying display.
LED 402 flashes twice, indicating the branch box is functioning as secondary unit 2 in a multi-unit setup. This is a normal status.
Operation LED blinks 2 times and Timer LED blinks 2 times (02) — Room temperature thermistor error.
The sensor that measures room temperature (thermistor) is detecting an abnormal temperature reading.
Operation LED blinks 2 times, Timer LED blinks 9 times, and wired remote shows 29 — Connection unit number error (indoor unit wired remote control).
The system has detected an incorrect number of connected indoor units, or an issue with the wired remote control address setting.
Operation LED blinks 3 times — Main relay error.
The outdoor unit is sending a signal even though the main relay is off, which indicates a problem with the main power relay.
Operation LED blinks 3 times and Timer LED blinks 3 times (04) — Indoor heat exchanger thermistor error.
The thermistor sensing the indoor heat exchanger temperature is reporting an abnormal reading.
Operation LED blinks 3 times and Timer LED shows 06 — Outdoor heat exchanger thermistor error.
The thermistor sensing the outdoor heat exchanger temperature is reporting an abnormal reading.
Operation LED blinks 3 times and Timer LED blinks 2 times (0C) — Discharge thermistor error.
The thermistor measuring the compressor's discharge temperature is detecting an abnormal reading.
Operation LED blinks 3 times, Timer LED blinks 10 times, and wired remote shows 3A — Indoor unit communication circuit (wired remote control) error.
There's a communication issue between the wired remote control and the indoor unit, or between multiple indoor units.
Operation LED blinks 3 times and Timer LED shows 18 — CT error (Current transfer error).
The current value during operation drops to zero amps one minute after the compressor starts, indicating a current transfer issue.
Operation LED blinks 3 times, Timer LED blinks 2 times, and wired remote shows 32 — Indoor unit PCB model information error (EEPROM error).
There is an error with the Electronically Erasable and Programmable Read Only Memory (EEPROM) on the indoor unit's controller PCB, which stores model information.
Operation LED blinks 3 times, Timer LED blinks 3 times, and wired remote shows 33 — Indoor unit motor electricity consumption detection error.
The indoor unit motor's voltage or current values have gone beyond their safe limits.
Operation LED blinks 3 times, Timer LED blinks 5 times, and wired remote shows 35 — Manual auto switch error.
The manual auto switch on the indoor unit is detected as being 'on' (pressed) for 60 or more consecutive seconds.
Operation LED blinks 3 times, Timer LED blinks 9 times, and wired remote shows 39 — Indoor fan motor power supply error.
There is an issue with the power supply to the indoor fan motor, possibly due to a voltage drop, electrical noise, or a connection problem.
Operation LED blinks 4 times — Power supply frequency error.
The system cannot recognize the power supply frequency within 4 seconds of being powered on, leading to a permanent stop.
Operation LED blinks 4 times and Timer LED shows 0A — Outdoor temperature thermistor error.
The thermistor measuring the outdoor ambient temperature is reporting an abnormal reading.
Operation LED blinks 4 times, Timer LED blinks 1 time, and wired remote shows 41 — Indoor room thermistor error.
The room temperature thermistor in the indoor unit is detecting an abnormal temperature.
Operation LED blinks 4 times and Timer LED blinks 2 times — Forced auto switch error.
The forced auto switch is detected as being held in the 'on' (pushed-in) position for 30 seconds or more.
Operation LED blinks 4 times, Timer LED blinks 2 times, and wired remote shows 42 — Indoor heat exchanger (pipe) thermistor error.
The thermistor that detects the temperature of the evaporator pipe in the indoor unit has identified an abnormal temperature.
Operation LED blinks 4 times, Timer LED blinks 4 times, and wired remote shows 44 — Human Sensor error.
There is an issue with the human presence sensor, potentially due to a loose connection, an open cable, or a faulty sensor/main PCB.
Operation LED blinks 5 times, Timer LED blinks 1 time, and wired remote shows 51 — Indoor unit fan motor error.
The indoor unit's fan motor is not rotating at at least one-third of its target speed for more than 56 seconds, or has stopped.
Operation LED blinks 5 times and Timer LED shows 1A — Compressor location error.
The compressor speed is not synchronizing with the control signal, or the compressor failed to start.
Operation LED blinks 5 times and Timer LED blinks 2 times (17) — IPM protection.
An abnormal current value is detected at the IPM (Intelligent Power Module), possibly due to blocked heat radiation.
Operation LED blinks 5 times, Timer LED blinks 3 times, and wired remote shows 53 — Drain pump error.
The float switch in the drain pump system has been activated for more than 3 minutes, indicating a blockage or pump malfunction.
Operation LED blinks 5 times, Timer LED blinks 7 times, and wired remote shows 57 — Damper error.
The limit switch did not detect the closing of the damper (upper airflow) even though the damper was commanded to close.
Operation LED blinks 5 times, Timer LED blinks 8 times, and wired remote shows 58 — Intake grille error.
The micro switch for the intake grille is detected as open while the compressor is running, meaning the grille may not be properly closed.
Operation LED blinks 6 times and Timer LED shows 1B — Outdoor fan error (DC motor).
An abnormal current or a fan motor lock error is detected in the outdoor unit's condenser fan motor.
Operation LED blinks 6 times, Timer LED blinks 2 times, and wired remote shows 62 — Outdoor unit main PCB error.
The outdoor unit's main control board (PCB) failed to access its memory (EEPROM) after starting up.
Operation LED blinks 6 times, Timer LED blinks 3 times, and wired remote shows 63 — Inverter error.
The system received error information from the transistor PCB (or inverter PCB), indicating a problem with the inverter circuit.
Operation LED blinks 6 times, Timer LED blinks 4 times, and wired remote shows 64 — PFC circuit error / Active filter error.
The inverter output DC voltage is too high (over 415V for 3+ seconds) or the inverter input DC voltage is too high (over 425V) or too low (below 80V) for certain models. This can also occur after a momentary power cut-off.
Operation LED blinks 6 times, Timer LED blinks 5 times, and wired remote shows 65 — IPM error.
An abnormal current value is detected at the IPM (Intelligent Power Module), potentially due to blocked heat radiation.
Operation LED blinks 7 times — VDD permanent STOP protection (electric air cleaner).
An error with the electric air cleaner has occurred, specifically after the air cleanness monitor protection operated 4 times.
Operation LED blinks 8 times and Timer LED shows 15 — Compressor temperature thermistor error.
The thermistor sensing the compressor temperature is detecting an abnormal reading.
Operation LED blinks 8 times and Timer LED shows 21 — Reverse VDD (electric air clean power supply circuit abnormal).
The air clean operation signal was detected for 1 minute when the air clean mode was actually off, indicating an issue with the electric air cleaner power supply circuit.
Operation LED blinks 2 times (Off) and Timer LED shows 01 — Serial reverse transfer error at startup.
When the system starts, the indoor unit (evaporator) and outdoor unit (condenser) are not communicating. This indicates a problem with the serial communication wiring.
Operation LED blinks 3 times (Off) and Timer LED shows 01 — Serial reverse transfer error during operation.
During normal operation, the indoor and outdoor units failed to communicate for 10 consecutive seconds. This indicates a communication issue.
Operation LED blinks 4 times (Off) and Timer LED shows 13 — Serial forward transfer error at startup.
At system startup, the indoor unit (evaporator) and outdoor unit (condenser) are not communicating.
Operation LED blinks 5 times (Off) and Timer LED shows 13 — Serial forward transfer error during operation.
During operation, the indoor and outdoor units failed to communicate for 10 consecutive seconds.
Operation LED blinks 8 times (Off) and Timer LED shows 00 — Wired remote controller communication error.
The indoor unit (evaporator) is not communicating with the wired remote controller.