Fujitsu · 410A Multi-Zone Mini-Split Systems
The limit switch did not detect the closing of the damper (upper airflow) even though the damper was commanded to close.
Click steps to track your progress.
Power off the indoor unit and visually inspect the damper for any obstructions that might prevent it from closing fully.
Manually check if the damper moves freely.
If comfortable, check the connector (CN18) and wiring for any looseness, shorts, or pinches.
Reset power to the unit. If the error persists, professional service is needed to check the limit switch or damper motor.