Operation 6 Times / Timer 1B

Operation LED blinks 6 times and Timer LED shows 1B — Outdoor fan error (DC motor).

Fujitsu · 410A Multi-Zone Mini-Split Systems

What does Operation 6 Times / Timer 1B mean?

An abnormal current or a fan motor lock error is detected in the outdoor unit's condenser fan motor.

Common Causes

  • Loose or defective fan motor connector.
  • The fan motor is locked or obstructed.
  • The controller PCB is defective.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Power off the unit at the circuit breaker and visually inspect the outdoor fan for any obstructions (debris, leaves) that might be preventing it from rotating.

  2. 2

    Gently try to rotate the fan blades by hand to ensure they move freely. (Ensure power is OFF before touching the fan.)

  3. 3

    Check the outdoor fan motor connector for any looseness or corrosion.

  4. 4

    If the problem persists, professional service is needed to check the fan motor or controller PCB.