Mitsubishi Electric · PWFY Air Conditioners
An overcurrent of 34.5Apeak or 16Arms or above is detected by the ACCT sensor. This indicates a significant electrical overload, potentially from incorrect wiring, fan issues, compressor failure, or a fault with the INV board.
Click steps to track your progress.
Check the inverter output wiring for proper and secure connections, ensuring correct polarity.
Inspect the fan wiring for any breakage, damage, or incorrect polarity.
Check the compressor for any earth faults or short circuits using appropriate testing equipment.
If no external wiring or compressor issues are found, the INV board may need replacement.
Contact a qualified technician for further diagnosis as internal inverter components are complex.