4250 (D101)

Error 4250 (Detail 101) – IPM (Intelligent Power Module) error

Mitsubishi Electric · PWFY Air Conditioners

What does 4250 (D101) mean?

An overcurrent condition is detected while the power module error detection signal is output. This indicates a problem within the inverter's intelligent power module, often due to wiring issues, compressor failure, or the INV board itself.

Common Causes

  • Improper inverter output wiring connection
  • Compressor failure (earth fault, short circuit)
  • Broken or damaged fan wiring, or incorrect wiring polarity
  • INV (Inverter) board failure

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Check the inverter output wiring for proper and secure connections, ensuring correct polarity.

  2. 2

    Inspect the fan wiring for any breakage, damage, or incorrect polarity.

  3. 3

    Check the compressor for any earth faults or short circuits using appropriate testing equipment.

  4. 4

    If no external wiring or compressor issues are found, the INV board may need replacement.

  5. 5

    Contact a qualified technician for further diagnosis as internal inverter components are complex.