4220 (D108)

Error 4220 (Detail 108) – Abnormal bus voltage drop detected

Mitsubishi Electric · PWFY Air Conditioners

What does 4220 (D108) mean?

A DC bus voltage of 200V or less is detected during inverter operation. This can be caused by power supply environment issues, a voltage drop within the system, or faults in the noise filter or INV board.

Common Causes

  • Power supply environment (e.g., instantaneous stop, power failure)
  • Voltage drop detected
  • Noise filter board fault
  • INV (Inverter) board failure

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Check the interphase power supply voltage to ensure it is 198V or above.

  2. 2

    Observe the bus voltage on the LED monitor during inverter operation.

  3. 3

    Check the wiring connections between the INV board, control board (CN631), ACL, noise filter board, and power supply terminal block (TB2).

  4. 4

    Inspect coils (L1-L3) for breakage and verify their resistance (20 Ω ± 5%).

  5. 5

    If the voltage across pins 1-3 of CN631 on the control board is 200V or above but the bus voltage is low, the control board may need replacement; otherwise, the INV board may be faulty.

Browse all codes in this manual (24)