A DC bus voltage of 200V or less is detected during inverter operation. This can be caused by power supply environment issues, a voltage drop within the system, or faults in the noise filter or INV board.
Click steps to track your progress.
Check the interphase power supply voltage to ensure it is 198V or above.
Observe the bus voltage on the LED monitor during inverter operation.
Check the wiring connections between the INV board, control board (CN631), ACL, noise filter board, and power supply terminal block (TB2).
Inspect coils (L1-L3) for breakage and verify their resistance (20 Ω ± 5%).
If the voltage across pins 1-3 of CN631 on the control board is 200V or above but the bus voltage is low, the control board may need replacement; otherwise, the INV board may be faulty.