Mitsubishi Electric · PWFY Air Conditioners
The system detects conditions indicating that the water-source heat exchanger is freezing. This error is critical and requires immediate corrective action to prevent damage to the heat exchanger, refrigerant piping, or surrounding property. A normal power reset will not clear this error in newer versions (Ver 1.24 and later).
Click steps to track your progress.
Check the pump for proper connection and operation, ensuring it is circulating water correctly.
Inspect thermistors TH6 and TH8, and their connectors for any disconnections or obvious faults.
Ensure there is no shortage of circulating water and the circulating refrigerant amount is correct.
To reset error 2135 (for Ver 1.24 and later): Set DipSW 1-8 of the relevant PWFY-AU unit from OFF to ON, then back to OFF to disable overwrite protection. Then, set DipSW 3-5 on the relevant PWFY-AU unit from OFF to ON. Shut down all power to the refrigerant system (OC, IC, AU, and BU). Set DipSW 3-5 on the relevant PWFY-AU from ON to OFF. Restore power to the entire refrigerant system.
Contact your local Mitsubishi distributor support representative if you have any questions or if the problem reoccurs, as failure to comply may void warranty coverage.