Mitsubishi Electric · PWFY Air Conditioners
The thermistor TH6, which monitors water temperature (inlet for BU), has detected a temperature of 85°C (185°F) or greater. This high temperature causes the unit to stop and enter a 3-minute restart delay mode.
Click steps to track your progress.
Verify that the pump is properly connected and functioning to ensure adequate water circulation.
Check the thermistor connector for TH6 to ensure it is securely plugged in and not loose or damaged.
If the connector is secure, the TH6 thermistor itself may be faulty and providing an incorrect temperature reading.
A qualified technician should confirm the actual water inlet temperature and potentially replace the TH6 thermistor if it's faulty.
Ensure proper water flow and temperature regulation within the system to prevent overheating.