Carrier Energy Recovery Ventilators

60 fault codes documented

1 Fault Code

Fault Code 1 — OVERCURRENT

The output current is excessive. This means the motor is drawing more current than it should.

2 Fault Code

Fault Code 2 — DC OVERVOLT

The intermediate circuit DC voltage is too high. This can happen during deceleration or due to power supply issues.

2 Red Flashes

2 Red Flashes — Limit Switch Fault

The system has detected a limit switch fault. The gas valve and igniter will be off, but the indoor fan and inducer will remain on.

3 Fault Code

Fault Code 3 — DEV OVERTEMP

The drive's heat sink is overheated, reaching or exceeding 115°C (239°F).

3 Red Flashes

3 Red Flashes — Flame Sense Fault

The control sensed a flame when the gas valve should be closed. The indoor fan and inducer will be on.

4 Fault Code

Fault Code 4 — SHORT CIRC

A short circuit fault has been detected. This is indicated by fault current.

4 Red Flashes

4 Red Flashes — Four Consecutive Limit Switch Faults

This indicates four consecutive limit switch faults occurred within a single heating cycle. No gas heating will occur.

5 Fault Code

Fault Code 5 — OVERLOAD

The drive is experiencing an inverter overload condition, meaning the output current exceeds its ratings.

5 Red Flashes

5 Red Flashes — Ignition Fault

The unit failed to ignite successfully after 15 minutes of attempts. No gas heating will occur.

6 Fault Code

Fault Code 6 — DC OVERVOLT

The intermediate circuit DC voltage is insufficient. This can occur if the input power is unstable.

6 Red Flashes

6 Red Flashes — Induced Draft Motor Fault

This fault relates to the induced draft motor. If the heat is off, there will be no gas heating. If heat is on, the gas valve will be off and the inducer will be on.

7 Fault Code

Fault Code 7 — Al1 LOSS

Analog input 1 has lost its signal. The value is less than the set limit.

7 Red Flashes

7 Red Flashes — Rollout Switch Lockout

The rollout switch has opened, causing a lockout. The gas valve and igniter are off, but the indoor fan and inducer are on.

8 Fault Code

Fault Code 8 — Al2 LOSS

Analog input 2 has lost its signal, falling below the set limit.

8 Red Flashes

8 Red Flashes — Internal Control Lockout

The IGC has detected an internal hardware or software error. No gas heating will occur.

9 Fault Code

Fault Code 9 — MOT OVERTEMP

The drive estimates that the motor is too hot. This can be due to overload or incorrect parameter settings.

9 Red Flashes

9 Red Flashes — Temporary Software Lockout

Electrical interference is disrupting the IGC software, causing a temporary lockout. No gas heating will occur.

10 Fault Code

Fault Code 10 — PANEL LOSS

Communication has been lost with the control panel. This fault occurs if the drive is in local control mode or if remote control mode is set to accept commands from the panel.

11 Fault Code

11 Fault Code — ID RUN FAIL

The motor identification run could not be completed successfully.

12 Fault Code

12 Fault Code — MOTOR STALL

The motor or process is stalled, operating in the stall region. This is usually due to excessive load or insufficient motor power.

14 Fault Code

14 Fault Code — EXT FAULT 1

The digital input configured for the first external fault is active.

15 Fault Code

15 Fault Code — EXT FAULT 2

The digital input configured for the second external fault is active.

16 Fault Code

16 Fault Code — EARTH FAULT

The load on the input power system is out of balance, indicating a potential earth fault.

17 Fault Code

17 Fault Code — UNDERLOAD

The motor load is lower than expected, suggesting a possible issue with the connected load.

18 Fault Code

18 Fault Code — THERM FAIL

An internal fault has occurred. The thermistor measuring the drive's internal temperature is open or shorted.

19 Fault Code

19 Fault Code — OPEX LINK

An internal fault has been detected related to communication between the OMIO and OINT boards.

A154

A154 — Serial EEPROM Hardware Failure

A hardware failure has occurred with the serial EEPROM, resulting in a unit shutdown.

A156

A156 — Critical Serial EEPROM Storage Fail Error

A critical failure in the serial EEPROM storage has occurred, causing a unit shutdown.

A157

A157 — A/D Hardware Failure

The Analog-to-Digital (A/D) hardware has failed, resulting in a unit shutdown.

A163

A163 — Circuit A Down Due to Failure Lockout

Circuit A is locked out due to accumulating three strikes or another alarm condition.

A164

A164 — Circuit B Down Due to Failure Lockout

Circuit B is locked out. This can occur after accumulating three fault strikes or being triggered by another alarm.

A200

A200 — Linkage Timeout Error — Comm Failure

A communication failure has occurred, indicated by a linkage timeout error. The system will fall back to local SPT operation.

A404 — Fire Shutdown

A404 — Fire Shutdown — Smoke Detected

The unit has shut down because smoke has been detected by a smoke detector.

ALARM GREEN LED FLASHING

Alarm (Green LED Flashing) — Advisory Diagnostic

For less severe errors (alarms), the drive flashes its green LED and displays an advisory message on the control panel. The drive is reporting an unusual condition.

D12 Green LED

D12 Green LED lit — ERV Wheel Status Alarm

This light indicates that the ERV wheel is not rotating when it should be. The system will signal an alarm.

D16 Green LED

D16 Green LED lit — ERV Dirty Filter Alarm

This light means the system has detected a dirty filter. This can affect the unit's performance.

D18 Green LED

D18 Green LED lit — ERV Blower Status Alarm

This indicates a blower or fan failure. The unit may not be able to move air effectively.

EXCB Motor Failure Alarm

EXCB Motor Failure Alarm — Intake or Exhaust Motor Problem

This alarm is triggered if the outside air or exhaust motor detects a problem, such as phase loss or thermal overload. The system will close its alarm contact, visible as 24vac at EXCB J8-3.

OAU LOW CFM

OAU LOW CFM — Not enough outside air is being drawn in

This alarm means the ERV is not achieving the desired amount of outside air. The actual outside air CFM is less than 10% of the commanded amount.

OAU Motor Failure Alarm

OAU Motor Failure Alarm — Intake or Exhaust Motor Problem

This alarm indicates a problem with one of the ERV's outside or exhaust motors. The system will signal this through the OAU Motor Failure Alarm point.

Red LED flashing

Red LED flashing — Fault condition requiring reset

A flashing red LED indicates a fault condition that requires a specific reset procedure.

T111

T111 — Circuit B Loss of Charge Lockout

This indicates a loss of charge in Circuit B, likely due to low refrigerant or a faulty pressure transducer.

T126

T126 — Circuit A High Discharge Pressure Shutdown

Circuit A has shut down due to high discharge pressure. This can be caused by several factors related to system overcharge or restrictions.

T127

T127 — Circuit B High Discharge Pressure Shutdown

Circuit B has shut down due to high discharge pressure. This is often related to system overcharge or airflow restrictions.

T133

T133 — Circuit A Low Refrigerant Pressure

This indicates low refrigerant pressure in Circuit A. Several factors can contribute to this condition.

T134

T134 — Circuit B Low Refrigerant Pressure

Circuit B is experiencing low refrigerant pressure. This can be caused by issues with refrigerant charge, airflow, or components.

T143

T143 — Circuit A Failure To Pressurize

Circuit A is failing to pressurize. This usually points to issues with compressor operation or wiring causing reverse rotation.

T144

T144 — Circuit B Failure To Pressurize

Circuit B is experiencing a failure to pressurize, often due to wiring issues affecting compressor rotation or a faulty compressor.

T153

T153 — Real Time Clock Hardware Failure

The unit's real time clock hardware has failed, meaning it cannot operate on its time and date schedule.

T155

T155 — Serial EEPROM Storage Failure Error

This error indicates a failure in the serial EEPROM's storage function, leading to unit operation errors.

T173

T173 — Loss of communication with the Energy Management Module

Communication has been lost with the Energy Management Module. The unit will not take any action related to it.

T175

T175 — Loss of communication with VFD

Communication has been lost with the Variable Frequency Drive (VFD), causing the unit to shut down.

T179

T179 — Loss of communication with the Economizer Control Board

Communication has been lost with the Economizer Control Board (ECB), resulting in no economizer operation.

T180

T180 — Loss of communication with the Economizer Actuator

There is no communication with the economizer actuator, meaning it will not operate.

T181

T181 — Loss of communication with Outside Air Unit

Communication with the Outside Air Unit (OAU) has failed, prompting a reset of OAU data.

T408

T408 — Dirty Air Filter

An alert has been generated because the air filter is dirty.

T409 Fan Status Switch

T409 — Fan Status Switch Fault

The fan status switch is indicating an incorrect state. This can lead to a unit shutdown if configured.

T410

T410 — R-W1 Jumper Not Installed in Space Temp Mode

The R-W1 jumper is not installed, preventing the unit from running heat in Space Temperature Mode.

T411

T411 — Thermostat Y2 Input Activated without Y1 Activated

The thermostat's Y2 input is activated while Y1 is not, causing the unit to run as if both Y1 and Y2 were on.

T418 OAU LOW CFM

T418 OAU LOW CFM — Not enough outside air is being drawn in

This alarm indicates that the ERV cannot bring in the desired amount of outside air. The actual outside air CFM is less than 10% of the commanded amount after 10 minutes.