Incorrect 015 coding

Incorrect Coding 015 - Boiler firing without circulation pump or DHW pump not energized

Viessmann · Vitodens 200 Boilers

What does Incorrect 015 coding mean?

Changing coding address 015 from its factory default can cause significant operational problems. For models 6-24C/6-24/8-32, changing to 015:001 results in the boiler firing without the circulation pump and solenoid valve. For models 11-44/15-60, changing to 015:000 results in the DHW pump not being energized. This may also lead to fault 02.

Common Causes

  • Incorrect modification of coding address 015 from its specified value

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    For models 6-24C, 6-24, 8-32, ensure coding address 015 is set to 015:000.

  2. 2

    For models 11-44, 15-60, ensure coding address 015 is set to 015:001.

  3. 3

    After making any changes, power cycle the boiler (power ON/OFF) for the new settings to take effect.

  4. 4

    If fault 02 appears, address coding 015 first as a potential cause.