Viessmann · Vitodens 200 Boilers
This fault indicates a problem with the boiler's ignition process or issues with the gas supply, especially common in new propane installations or after extended periods of inactivity.
Click steps to track your progress.
Extensively purge the gas line, especially for new propane installations or if the boiler has been off for a long time.
Verify the gas regulator and the working inlet gas pressure (not static pressure).
Check the ionization current and the gaps of the ionization rod.
If comfortable, check the input voltage to the ionization rod (approx. 160-170 VAC to ground) and power supply polarity (L, N, G).
If the issue persists, a professional should check the resistance of the gas valve coils and the spark/ignition transformer.