CodeRegistry
Brands
  1. Home
  2. SolarEdge
  3. ESS Systems
  4. Input current-limit setting
About·Privacy·Terms

CodeRegistry — Your global library for technical solutions.

For your safety: always follow the equipment manufacturer’s official manuals. CodeRegistry is an independent help site and is not affiliated with the brands listed here.

Input current-limit setting

Input current-limit setting — Loads must be on AC-out for limiter to work

SolarEdge · ESS Systems

What does Input current-limit setting mean?

The Input current-limit setting in VEConfigure functions as a threshold for AC current at the AC-in of the Multi/Quattro. For this limiter to be effective, all loads should be installed on the AC-out of the unit.

Common Causes

  • Loads connected in parallel with the Multi/Quattro bypass the current limiter.
  • The current limiter is intended for AC-in current, not total system load.
  • ESS installation disables PowerAssist and Dynamic current limiter.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Install all intended loads on the AC-out terminals of the Multi or Quattro.

  2. 2

    Ensure the AC Input Current limiter setting accurately reflects the desired maximum current.

  3. 3

    Understand that this setting applies to current in both directions.

  4. 4

    Note that PowerAssist and Dynamic current limiter settings are ignored when ESS is installed.

Browse all codes in this manual (12)
Verified technical data. Last updated: April 2026

Related Faults

Battery discharging then charged every nightBattery discharging then charged every night — Potential Sustain protection or SOC settingESS Relay test PendingESS Relay test Pending — Feed-in disabled until test completesLoads powered by grid, not battery or solarLoads powered by grid, not battery or solar — Check battery SOC, limits, and relay test
Source: SolarEdge ESS Systems
Open Manual (Page 11)Search more codes in this manual