Mitsubishi Heavy Industries R410A Systems

60 fault codes documented

E0

E0 - Transmitting/receiving signal error

A communication error has occurred between internal components, likely between the indoor and outdoor units or control boards. This prevents proper system operation.

E12

E12 - Auto address setting error or unit addressed at factory setting

The system detected an issue during the auto-addressing process, or one or more units (indoor or outdoor) are still set to factory default addresses (48 or 49). Auto-addressing may not be possible on certain systems.

E14

E14 (Flashes 3 times) - Master/slave system control wiring error

The system displays E14 and the LED flashes 3 times, indicating a problem with the control wiring between the master and slave units. This could be an incorrect DIP switch setting or an open circuit in the wiring.

E16

E16 - Faulty indoor fan motor

A fault has been detected with the indoor unit's fan motor, preventing it from operating correctly. This can lead to poor airflow and inefficient cooling/heating.

E28

E28 - Remote controller sensor failure

The sensor within the remote controller has failed. This sensor is typically used to read the ambient temperature at the remote control's location, impacting temperature regulation.

E30

E30 - Indoor/outdoor unit connected error

There is an error related to the connection between the indoor and outdoor units. This indicates a problem in the communication or wiring that links these two main components.

E31

E31 - Duplication of indoor unit address number or outdoor unit address setting error

This error indicates that an indoor unit has a duplicate address number (U00-U47) or there is an error in the outdoor unit's address setting. Each unit must have a unique address in a multi-system setup.

E32

E32 - Anti-phase device detected swapped or open L2 phase

The anti-phase device has detected that two phases of the mains power need to be swapped, or the L2 phase of the mains power (primary side of contactor) has been detected as open. This is a critical power supply issue.

E34

E34 - Abnormally low current detected by CT on L3 or open phase at L3

The current transformer (CT) on the L3 phase has detected abnormally low current, or no current at all. This indicates a power supply issue on the L3 phase.

E35

E35 - Outdoor unit heat exchanger sensor (ThOR) defective or cooling high pressure

The outdoor unit's heat exchanger sensor (ThOR) is detected as defective (open or closed circuit), or there is abnormally high pressure in the cooling circuit.

E36

E36 - Abnormally high discharge temperature or faulty THOD sensor

The discharge temperature is abnormally high, or the compressor discharge temperature sensor (THOD) is defective. High discharge temperatures indicate system strain.

E37

E37 - Outdoor unit heat exchanger sensor (ThOR) defective

The outdoor unit's heat exchanger sensor (ThOR) has an open circuit or a poor connection, preventing accurate temperature readings. This general error code encompasses more specific thermistor failures (E37-1 to E37-6).

E37-1

E37-1 - Outdoor heat exchanger thermistor failure (Tho-R1)

The outdoor unit's heat exchanger thermistor (Tho-R1) has failed. This thermistor is critical for measuring the temperature of the heat exchanger, impacting unit operation.

E37-2

E37-2 - Outdoor heat exchanger thermistor failure (Tho-R2)

The outdoor unit's heat exchanger thermistor (Tho-R2) has failed. This thermistor is critical for measuring the temperature of the heat exchanger, impacting unit operation.

E37-3

E37-3 - Outdoor heat exchanger thermistor failure (Tho-R3)

The outdoor unit's heat exchanger thermistor (Tho-R3) has failed. This thermistor is critical for measuring the temperature of the heat exchanger, impacting unit operation.

E37-4

E37-4 - Outdoor heat exchanger thermistor failure (Tho-R4)

The outdoor unit's heat exchanger thermistor (Tho-R4) has failed. This thermistor is critical for measuring the temperature of the heat exchanger, impacting unit operation.

E37-5

E37-5 - Outdoor heat exchanger thermistor failure (Tho-R5)

The outdoor unit's heat exchanger thermistor (Tho-R5) has failed. This thermistor is critical for measuring the temperature of the heat exchanger, impacting unit operation.

E37-6

E37-6 - Outdoor heat exchanger thermistor failure (Tho-R6)

The outdoor unit's heat exchanger thermistor (Tho-R6) has failed. This thermistor is critical for measuring the temperature of the heat exchanger, impacting unit operation.

E38

E38 - Outside air temperature sensor (ThoA) defective

The outside air temperature sensor (ThoA) is defective, either due to an open circuit or a poor connection on the outdoor unit PCB. This prevents the system from accurately reading ambient outdoor temperatures.

E39

E39 - Compressor discharge temperature sensor (ThOD) defective

The compressor discharge temperature sensor (ThOD) has a defective resistance (open circuit) or a poor connection on the outdoor unit PCB. This sensor monitors the temperature of the refrigerant leaving the compressor.

E40

E40 - High-pressure switch (B3H or 63H1) tripped, or airflow issue

The high-pressure switch (B3H or 63H1) has tripped, indicating abnormally high pressure in the refrigerant system. This could be due to an overcharge, closed service valves, or insufficient airflow over the condenser coil.

E41

E41 - Inverter power transistor overheated

The power transistor for the inverter has overheated. This indicates a problem with the inverter board, often due to excessive load, poor ventilation, or component failure.

E42

E42 - Abnormally high current detected in compressor

Abnormally high current has been detected in the compressor, indicating it is working too hard or experiencing an electrical fault. This is a protective shutdown.

E43

E43 - Maximum number of indoor units connected exceeded

The maximum number of indoor units allowed for connection to one outdoor unit has been exceeded. This is an installation configuration error.

E45

E45 - Transmission error between inverter and outdoor unit PCB or loose connection

A transmission error has occurred between the inverter and the outdoor unit's Printed Circuit Board (PCB), or there is a loose connection at the "Cal" point. This affects communication between critical components.

E46

E46 - Address settings conflict (automatic/manual/remote control addresses coexist)

There is a conflict in address settings where automatic, manual, and/or remote control addresses are coexisting on one network. This leads to communication issues in multi-unit systems.

E47

E47 - Inverter over voltage

The inverter has detected an overvoltage condition. This means the incoming electrical voltage to the inverter is too high, which can damage components.

E48

E48 - DC Outdoor Fan motor fault

A fault has been detected in the DC outdoor fan motor. This prevents the outdoor unit from properly dissipating heat, leading to system inefficiencies or shutdowns.

E49

E49 - Low pressure fault or low voltage detected

The system has detected either a low pressure fault in the refrigerant system or a low voltage condition. Both can impair system performance and lead to protective shutdowns.

E51

E51 - Inverter PCB fault or power transistor overheat

There is a fault with the inverter PCB itself, or the power transistor on the inverter board has overheated. Both indicate a serious internal electronic issue.

F1

F1 - Reverse phase detected

The outdoor unit has detected that the electrical phases are reversed. This indicates an issue with the power supply wiring to the outdoor unit.

F2

F2 - L3 open phase detected

The system has detected an open phase on the L3 power line, typically affecting the outdoor unit. This means there is a loss of power on one of the electrical phases.

F3

F3 - 63L connector open

This error indicates that the 63L connector, likely associated with the outdoor unit, is open or disconnected. This is often a wiring issue.

F4

F4 - 49C connector open

An open or disconnected 49C connector has been detected in the outdoor unit. This suggests a problem with a specific electrical connection.

F7

F7 - Reverse phase detector circuit (p.c.board) fault

A fault has been detected in the reverse phase detector circuit on the main printed circuit board (PCB) of the outdoor unit. This is an internal electronic fault.

F8

F8 - Input circuit fault

An input circuit fault has been detected in the outdoor unit. This generally points to a problem with the electrical power input to the system.

F9

F9 - Connector 2 or more open

This error means that two or more connectors, likely within the outdoor unit, are open or disconnected. This points to multiple wiring issues or a more general problem.

FA

FA - L2-phased open phase or 51CM connector open

The system has detected an open phase on the L2 power line or an open 51CM connector. This indicates a power supply or connection issue on one of the phases.

P1

P1 - Intake air sensor abnormal

The intake air sensor in the indoor unit, which measures the temperature of the air entering the system, is reporting an abnormal reading. This can lead to incorrect temperature control.

P2

P2 - Pipe sensor abnormal

A pipe sensor, likely measuring refrigerant temperature on a pipe within the indoor unit, is reporting an abnormal condition. This affects the system's ability to monitor refrigerant flow.

P3

P3 - System error (Transmitting/receiving signal)

This indicates a system communication error between components, similar to an E0 error. It means signals are not being sent or received correctly, impairing system control.

P4

P4 - Drain sensor abnormal

The drain sensor has detected an abnormal condition, usually indicating a problem with the condensate drain system. This could lead to water overflow.

P5

P5 - Drain overflow protection mechanism malfunctioning

The system's drain overflow protection mechanism has malfunctioned. This means the unit is unable to properly prevent condensate water from overflowing, which could lead to water damage.

P6

P6 - Abnormality of coil frost/overheating protection modes

An abnormality has been detected in the coil frost or overheating protection modes. This indicates the system is either freezing up or overheating, and its safety mechanisms are not functioning correctly.

P7

P7 - System error (Address)

An address system error has occurred, which typically happens in multi-unit systems where each unit requires a unique address for communication. This indicates a conflict or misconfiguration.

P8

P8 - Outdoor unit malfunction

A general malfunction has been detected in the outdoor unit. This broad error indicates that a component within the outdoor unit is not operating as expected.

U1-1

U1 - Abnormal high pressure (High pressure switch 63H activated)

The system has detected excessively high pressure in the refrigerant circuit, triggering the high-pressure switch (63H) as a safety measure. This can lead to system shutdown.

U1-2

U1 - Direct cut operation triggered

The unit has performed a "direct cut" shutdown, indicating a protective measure due to an detected internal fault. This could be related to electrical stability or sensor readings.

U2-1

U2 - Abnormal high discharging temperature

The outdoor unit has detected an abnormally high discharge temperature. This often indicates the system is working under strain, possibly due to blockages or low refrigerant.

U2-2

U2 - Inner thermostat (49C) operation activated

The inner thermostat (49C) in the outdoor unit has activated, likely due to an internal overheat condition. This triggers a safety shutdown to prevent damage.

U3

U3 - Discharge thermistor short/open

The discharge thermistor, which measures the temperature of the refrigerant leaving the compressor, is either short-circuited or open. This prevents accurate temperature readings.

U4-1

U4 - Overheat protection activated

The system has initiated an overheat protection shutdown. This occurs when internal temperatures exceed safe operating limits, often due to restricted airflow or system strain.

U4-2

U4 - Outdoor thermistor short/open circuit

The outdoor thermistor, which measures the ambient temperature, has a short or open circuit. This prevents the system from accurately sensing external conditions, affecting performance.

U6

U6 - Compressor over current (Overload) cut off

The compressor has drawn too much current, triggering an overload protection shutdown. This indicates the compressor is working too hard or has an electrical fault.

UA

UA - Compressor over current (Terminal relay operation)

The compressor has experienced an overcurrent condition related to the terminal relay, causing a shutdown. This suggests an electrical issue with the compressor's starting or running circuit.

UE

UE - High pressure error (ball valve closed)

A high-pressure error has occurred, specifically indicating that a ball valve is closed, restricting refrigerant flow. This causes pressure to build up in the system.

UF-1

UF - Compressor over current (start-up locked) cut off

The system detected excessive current drawn by the compressor during startup, causing a safety shutdown. This typically means the compressor motor is unable to begin operating.

UF-2

UF - Compressor over current (operating locked) cut off

The compressor experienced an overcurrent condition while running, leading to a safety shutdown. This suggests a mechanical problem or excessive load on the compressor during operation.

UH

UH - Current sensor error

A fault has been detected in the current sensor, which monitors the electrical current within the system. This can lead to incorrect readings or safety shutdowns.

UL

UL - Abnormal low pressure

The system has detected abnormally low pressure in the refrigerant circuit. This usually points to a lack of refrigerant or a blockage.