Mitsubishi Electric · PUMY Air Conditioners
This indicates that the air conditioner system has detected abnormally high pressure, either through the high-pressure switch (63H) or the high-pressure sensor (63HS). This can trigger a shutdown to protect the system.
Click steps to track your progress.
Turn OFF the air conditioner's power supply before proceeding with any checks.
Verify that the outdoor stop valves (liquid/gas lines) are fully open. If closed, open them completely.
Check if the outdoor fan motor is rotating properly during operation and clear any obstructions around the outdoor unit.
Inspect the outdoor heat exchanger for dirt, debris, or blockages and clean it if necessary.
Check if the indoor fan motor is rotating properly and ensure indoor unit filters are clean and free of obstructions.
If the problem persists, contact a qualified service technician as internal components like sensors, valves, or control boards may be faulty.