This code indicates that the compressor's temperature (detected by thermistor TH4) has become excessively high, either continuously exceeding 110°C (230°F) for 5 minutes or momentarily going above 125°C (257°F). This signifies that the compressor is overheating, which can lead to severe damage.
Click steps to track your progress.
Ensure the outdoor stop valve (liquid/gas) is fully open. These valves should be completely open during operation to allow proper refrigerant flow.
Check for any visible signs of refrigerant leaks around the outdoor unit or piping connections, as low refrigerant can cause the compressor to overheat.
Turn off the main power to the unit at the circuit breaker, wait for a few minutes, then turn it back on to reset the system.
If the issue persists, a qualified HVAC technician should be contacted to check for refrigerant leaks, inspect the system for clogs, and evaluate the thermistor and valves.