Lennox · EL18KSLV Series Outdoor Units
The 4-way valve is responsible for directing hot gas. If it fails to shift correctly, temperature sensors will detect a problem and trigger an error code.
Click steps to track your progress.
Check for correct refrigerant charge and that all other operating parameters are met.
In heating mode, check for line voltage to the solenoid coil after the time delay.
If voltage is present but the valve doesn't shift, unplug the valve from the PCB.
Use an ohmmeter to check the solenoid coil for continuity. If resistance is out of spec, replace the coil.
Use a strong magnet along the valve body to check if the piston is stuck. If stuck, the valve must be replaced.