10

Error 10 — Outdoor defrost sensor failure

Lennox · EL18KSLV Series Outdoor Units

What does 10 mean?

There is an electrical failure with the sensor that measures the outdoor coil temperature during defrost cycles. This sensor is connected to the PCB.

Common Causes

  • Sensor short circuit
  • Sensor open circuit
  • Loose sensor connection
  • Defective sensor

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Check the connection of the outdoor defrost sensor to the PCB.

  2. 2

    Inspect the sensor wiring for damage.

  3. 3

    Use an ohmmeter to test the sensor's resistance against the temperature resistance table.

  4. 4

    Replace the sensor if it is faulty.