Haier Hydro Split & All-in-One Systems

60 fault codes documented

E01

E01 — HU Water Inlet Temperature sensor Abnormality

This error indicates a problem with the water inlet temperature sensor in the Hydro Unit (HU). The sensor might be disconnected or have an electrical fault (open or short circuit).

E02

E02 — HU Water Outlet Temperature sensor Abnormality

This error indicates a problem with the water outlet temperature sensor in the Hydro Unit (HU). The sensor might be disconnected or have an electrical fault (open or short circuit).

E03

E03 — HU Liquid Pipe Temperature sensor Abnormality

This error indicates a problem with the liquid pipe temperature sensor in the Hydro Unit (HU). The sensor might be disconnected or have an electrical fault (open or short circuit).

E04

E04 — HU Gas Pipe Temperature sensor Abnormality

This error indicates a problem with the gas pipe temperature sensor in the Hydro Unit (HU). The sensor might be disconnected or have an electrical fault (open or short circuit).

E05

E05 — EEPROM Abnormality

This error indicates a problem with the EEPROM (Electrically Erasable Programmable Read-Only Memory) in the indoor unit, suggesting an internal communication or data storage issue.

E06

E06 — Communication Error between Outdoor Unit and Indoor Unit

The indoor unit is not receiving communication signals from the outdoor unit for more than 2 minutes, indicating a break in communication.

E07

E07 — Communication Error between Remote Wired Controller and Indoor Unit

The indoor unit is not receiving correct data from the remote wired controller for 4 consecutive minutes, indicating a communication breakdown with the controller.

E08

E08 — Flow Switch Abnormality / Low Water Flow

This error occurs if no water flow signal is detected after the water pump operates for 120 seconds, or if the water flow is lower than the set value. It can be caused by issues like crystallization on the pump rotor, especially after extended shutdown or with poor water quality.

E09

E09 — Indoor Unit Address Duplication Abnormality

This error indicates that there is a conflict in the address settings for the indoor units, meaning two or more units might be set to the same address.

E10

E10 — DHW Tank Temperature sensor Abnormality

This error indicates a problem with the Domestic Hot Water (DHW) tank temperature sensor. The sensor might be disconnected or have an electrical fault (open or short circuit).

E11

E11 — I/O PCB Communication Abnormality

This error indicates that the communication signal from the I/O (Input/Output) board cannot be received for 2 minutes, suggesting a problem with the board or its connection.

E12

E12 — HU ZONE2 Water Mixing Valve Temperature sensor Abnormality

This error indicates a problem with the temperature sensor for the water mixing valve in Hydro Unit Zone 2. The sensor might be disconnected or have an electrical fault (open or short circuit).

E13

E13 — Water Leakage Detected (Reserved)

This error indicates that the micro switch input continuously detects water for 60 seconds, signaling a water leakage.

E14

E14 — Low Pressure Switch Abnormality (Reserved)

This error indicates that the low pressure switch (LP) has disconnected for 5 seconds, typically due to a very low flow rate in the system.

E15

E15 — Anti-freeze Abnormality

This error indicates that the system has detected conditions leading to anti-freeze protection activation, such as very low water temperatures in cooling mode.

E16

E16 — HU Water Inlet/Outlet Temperature Over High

This error indicates that the water temperature at either the inlet (Twi) or outlet (Two) of the Hydro Unit has exceeded 82°C for 5 seconds, triggering an overheating protection.

E17

E17 — HU ZONE1 Ambient Temperature sensor Abnormality

This error indicates a problem with the ambient temperature sensor for Hydro Unit Zone 1. The sensor might be disconnected or have an electrical fault (open or short circuit).

E18

E18 — HU ZONE2 Ambient Temperature sensor Abnormality

This error indicates a problem with the ambient temperature sensor for Hydro Unit Zone 2. The sensor might be disconnected or have an electrical fault (open or short circuit).

E19

E19 — Pool Mixing Valve Water Outlet/Pool Water Temperature sensor Abnormality

This error indicates a problem with the temperature sensor connected to the pool mixing valve water outlet or the pool water. The sensor might be disconnected or have an electrical fault (open or short circuit).

E20

E20 — General Outdoor Unit Abnormality

This code indicates a general malfunction or abnormal condition within the outdoor unit, without specifying a particular component.

E20-0

E20-0 — Outdoor Condenser Defrosting Coil Temperature sensor Te1 Abnormality

This error indicates a problem with the outdoor condenser defrosting coil temperature sensor Te1. The sensor might be disconnected or have an electrical fault (open or short circuit).

E20-1

E20-1 — Outdoor Condenser Defrosting Coil Temperature sensor Te2 Abnormality

This error indicates a problem with the outdoor condenser defrosting coil temperature sensor Te2. The sensor might be disconnected or have an electrical fault (open or short circuit).

E21

E21 — Outdoor Ambient Temperature sensor Abnormality

This error indicates a problem with the outdoor ambient temperature sensor. The sensor might be disconnected or have an electrical fault (open or short circuit).

E22

E22 — Outdoor Compressor Suction Temperature sensor Abnormality

This error indicates a problem with the outdoor compressor suction temperature sensor. The sensor might be disconnected or have an electrical fault (open or short circuit).

E23

E23 — Compressor Discharge Temperature sensor Abnormality

This error indicates a problem with the compressor discharge temperature sensor. The sensor might be disconnected or have an electrical fault (open or short circuit).

E24

E24 — Compressor Oil Temperature sensor Toil Abnormality

This error indicates a problem with the compressor oil temperature sensor (Toil). The sensor might be disconnected or have an electrical fault (open or short circuit).

E27

E27 — Oil Temperature Over High Protection (Toil)

This error indicates that the compressor oil temperature (Toil) has exceeded 110°C, triggering an over-high protection. If this occurs 3 times in an hour, the failure will be confirmed as unresumable.

E28

E28 — Compressor Discharge Pressure sensor Abnormality

This error indicates a problem with the compressor discharge pressure sensor. The sensor might be disconnected or have an electrical fault (open or short circuit).

E29

E29 — Compressor Suction Pressure sensor Abnormality

This error indicates a problem with the compressor suction pressure sensor. The sensor might be disconnected or have an electrical fault (open or short circuit).

E30

E30 — High Pressure Switch HPS Abnormality

This error indicates that the high pressure switch (HPS) has disconnected, signaling an abnormal high pressure condition in the system. If this occurs 3 times in an hour, the failure will be confirmed as unresumable.

E32-0

E32-0 — Outdoor Subcooling Coil Outlet Temperature sensor Abnormality

This error indicates a problem with the outdoor subcooling coil outlet temperature sensor. The sensor might be disconnected or have an electrical fault (open or short circuit).

E32-1

E32-1 — Outdoor Liquid Pipe Subcooling Temperature sensor Abnormality

This error indicates a problem with the outdoor liquid pipe subcooling temperature sensor. The sensor might be disconnected or have an electrical fault (open or short circuit).

E33

E33 — Outdoor Unit PCB EEPROM Abnormality

This error indicates a communication failure with the EEPROM (Electrically Erasable Programmable Read-Only Memory) on the outdoor unit's PCB (Printed Circuit Board). This is an unresumable fault.

E34

E34 — Compressor Discharge Temperature Over High Protection (Td)

This error indicates that the compressor discharge temperature (Td) has exceeded 115°C, triggering an over-high protection. If this occurs 3 times in an hour, the failure will be confirmed as unresumable.

E35

E35 — Four Way Valve Reversing Abnormality

This error indicates a problem with the four-way valve failing to reverse correctly, which impacts the unit's ability to switch between heating and cooling modes. If this occurs 3 times in an hour, the failure will be confirmed as unresumable.

E36

E36 — Oil Temperature Over Low Protection (Toil)

This error indicates that the compressor oil temperature (Toil) has remained too low for 5 continuous minutes, triggering an over-low protection. If this occurs 3 times in an hour, the failure will be confirmed as unresumable.

E38

E38 — High Pressure Over Low Protection

This error indicates that the system's high pressure has been detected as abnormally low for 5 minutes. If this occurs 3 times in an hour, the failure will be confirmed as unresumable.

E39-0

E39-0 — Low Pressure Over Low Protection

This error indicates that the system's low pressure (Ps) has been detected as abnormally low for 5 minutes during either cooling or heating operation. If this occurs 3 times in an hour, the failure will be confirmed as unresumable.

E39-1

E39-1 — Compression Ratio Over High Protection

This error indicates that the compressor's compression ratio has exceeded 10.0 for one continuous minute after starting, leading to a shutdown and alarm.

E40

E40 — High Pressure Over High Protection

This error indicates that the system's high pressure (Pd) has exceeded 41.5 kg or a critical temperature (Pd_temp) for 5 consecutive minutes. If this occurs 3 times in an hour, the failure will be confirmed as unresumable.

E43

E43 — Compressor Discharge Temperature sensor Over Low Protection

This error indicates that the compressor discharge temperature (Td) is abnormally low during normal operation (Td < Pd+10℃ for 5 minutes). If this occurs 3 times in an hour, the failure will be confirmed as unresumable.

E46

E46 — Communication Error with Driver PCB

This error indicates that the module board signal is not being received or contains incorrect data for 30 consecutive seconds. The system will automatically restore itself if correct data is received.

E49

E49 — Low Pressure Switch Abnormality

This error indicates that the low pressure switch (LP) has disconnected for 5 seconds, reporting a fault. If this occurs 3 times in an hour, the failure will be confirmed as unresumable.

E51-0

E51-0 — LEVa Overcurrent Protection

This error indicates that the LEVa driver chip has detected an overcurrent condition.

E51-2

E51-2 — LEVb Overcurrent Protection

This error indicates that the LEVb driver chip has detected an overcurrent condition.

E52-0

E52-0 — LEVa Disconnection Abnormality

This error indicates a problem with the LEVa (Liquid Electronic Valve) connection, likely a disconnection detected by the LEV driver chip.

E52-2

E52-2 — LEVb Disconnection Abnormality

This error indicates a problem with the LEVb (Liquid Electronic Valve) connection, likely a disconnection detected by the LEV driver chip.

E53

E53 — CT Current Over Low or Current sensor Abnormality

This error indicates that the compressor's current sensor sampling value is too low after operating at a high frequency (>= 50Hz) for 5 minutes, or there is an issue with the current sensor itself.

E54

E54 — Communication Error with Subcooling Module

This error indicates that the signal from the subcooling module board is not received or contains incorrect data for 2 consecutive minutes. The system will automatically restore itself if correct data is received.

E57

E57 — Communication Error between Subcooling Module and Main PCB

This error, sent by the subcooling module, indicates a communication failure between the subcooling module and the main PCB (Printed Circuit Board).

E58

E58 — Subcooling Module Tc1 Temperature sensor Error

This error, sent by the subcooling module, indicates that the subcooling module is not connected to the Tc1 temperature sensor.

E59

E59 — Subcooling Module Tc2 Temperature sensor Error

This error, sent by the subcooling module, indicates that the subcooling module is not connected to the Tc2 temperature sensor.

E63

E63 — Subcooling Module Dip Switch Error

This error occurs when the system detects a subcooling module, but the dip switch setting for the subcooling module is incorrect or not configured. This is an unresumable fault.

E64

E64 — CT Current Over High

This error indicates that the CT (Current Transformer) current has exceeded the specified value for 5 consecutive seconds, indicating an electrical overload. If this occurs 3 times in an hour, the failure will be confirmed as unresumable.

E65

E65 — Electrical Control Box Temperature sensor (Tb) Abnormality

This error indicates a problem with the electrical control box temperature sensor (Tb). The sensor might be disconnected or have an electrical fault (open or short circuit).

E68

E68 — Communication Error with DHW I/O PCB

This error indicates that the signal from the DHW (Domestic Hot Water) I/O PCB is not received or contains incorrect data for 2 consecutive minutes. The system will automatically restore itself if correct data is received.

E69

E69 — DHW I/O PCB Tank Temperature Abnormality

This error indicates a problem with the DHW (Domestic Hot Water) I/O PCB's tank temperature sensor. The sensor might be disconnected or have an electrical fault (open or short circuit).

E70

E70 — DHW I/O PCB Other Abnormalities

This is a reserved error code indicating a general abnormality with the DHW (Domestic Hot Water) I/O PCB.

E71-0

E71-0 — Upper DC Fan Motor Abnormality

This error indicates a problem with the upper DC fan motor, specifically if its operation is below 20 rpm for 40 seconds or less than 20% of the target value. If this occurs 3 times in an hour, the failure will be confirmed as unresumable.

E71-1

E71-1 — Lower DC Fan Motor Abnormality

This error indicates a problem with the lower DC fan motor, specifically if its operation is below 20 rpm for 40 seconds or less than 20% of the target value. If this occurs 3 times in an hour, the failure will be confirmed as unresumable.