Compressor discharge temperature has exceeded 115°C. The error clears if the temperature drops below 115°C within 3 minutes. It locks if it occurs 3 times in 1 hour.
Click steps to track your progress.
Check if sensor wiring is firmly in place.
Check if the system is clogged and clean the piping system.
Check if the system is low on refrigerant and charge it if necessary.
Check if the PMV coil wiring is okay and if the stop valve is open.
Replace wire and test again if sensor resistance is not within range.