The high pressure switch circuit has been detected as open for 30 seconds after 3 minutes of compressor runtime. This error locks if it happens 3 times in 1 hour.
Click steps to track your progress.
Power off and check if the pressure switch connection is okay.
Use a multimeter to check if the high pressure switch terminal is short circuit.
Check if the EEV coil is fully seated and reconnect it.
Open the service valve and check if the piping system is clogged or if the connection pipe is bent.
Replace the pressure switch if it is bad. Replace the sensor if it is bad.