Fronius · Primo GEN24 Inverters
Status code 1173, with a flashing red operating LED, indicates that an electric arc has been detected in the PV system. The inverter has reached its maximum number of automatic connection attempts within 24 hours.
Click steps to track your progress.
Before confirming the status, visually check the entire photovoltaic system for any possible damage.
Press the optical sensor on the inverter for 3 seconds (max. 6 seconds) to acknowledge the fault.
Confirm the '1173 - ArcContinuousFault' status on the inverter's user interface (System > Event Log or Notifications menu).
If damaged components are found or the fault recurs, have them repaired by qualified specialists.