Carrier · VVT-1T System
A Storage Failure (SF) error, specifically SF 16, indicates that the slave thermostat's stored Airflow Set Point has been corrupted or lost. The system will default to a value of 0. This set point determines the desired airflow for the zone.
Click steps to track your progress.
Establish communications with the slave thermostat using the PC Command Center software.
Initiate a Device Inquiry for the slave thermostat to verify its current settings.
Perform the 'Modify Device Information' command and navigate to the Airflow Set Point setting.
Re-enter the correct airflow set point for the zone.
Press F1 to 'Perform Update' and wait for acknowledgement to save the new setting.
Exit the configuration menu and program, then verify the airflow set point is correctly stored.