Carrier · VVT-1T System
The slave thermostat display shows four zeros that either blink on and off or are constantly displayed. This means the thermostat is repeatedly cycling through its power-up sequence and cannot enter normal operating mode.
Click steps to track your progress.
Check the voltage from the 24 VAC transformer; it should be between 22 and 30 VAC.
Verify there is a steady 10 VDC across the red and white wires coming from the damper actuator.
Inspect the yellow and blue wires from the damper actuator to the slave thermostat wiring connector board for breaks or disconnections.
Ensure the slave thermostat ribbon cable is properly installed and not defective; disconnect and reseat it if necessary.
Refer to the 'Slave Thermostat Wiring' section on page 9 for further troubleshooting of the ribbon cable and wiring connector block.