Bryant · Comfort Alert Diagnostic Module
This indicates a short circuit or an over-current condition on the PROT terminal. The load on this circuit should not exceed 1 Amp.
Click steps to track your progress.
Turn off unit power supply and install a lockout tag.
Inspect the compressor contactor coil for shorts.
Verify the load on the PROT terminal is within the 1 Amp limit.
Check wiring to ensure 24 VAC is not directly connected to the PROT terminal.