ALERT LED * flashes Yellow (misreported)

Yellow ALERT LED * flashes (misreported) — Welded Contactor check

Bryant · Comfort Alert Diagnostic Module

What does ALERT LED * flashes Yellow (misreported) mean?

This indicates a potential misreporting of the 'Welded Contactor' code. Confirm the Y terminal connection and voltage.

Common Causes

  • Module's Y terminal is not connected.
  • Incorrect Y terminal connection.
  • Contactor coil not dropping below 0.5VAC when off.
  • R and C are reverse wired.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Turn off unit power supply and install a lockout tag.

  2. 2

    Determine if the module's Y terminal is properly connected.

  3. 3

    Verify the Y terminal is connected to 24VAC at the contactor coil.

  4. 4

    Check that the voltage at the contactor coil falls below 0.5VAC when off.

  5. 5

    Confirm that R and C terminals are not reverse wired.

  6. 6

    Ensure 24VAC is present across Y and C when the thermostat demands operation.

Browse all codes in this manual (55)
Verified technical data. Last updated: April 2026

Related Faults

ALERT LED 2 flashes YellowYellow ALERT LED 2 flashes — System pressure trip or compressor overloadALERT LED 3 flashes YellowYellow ALERT LED 3 flashes — Compressor short cyclingALERT LED 3 flashes Yellow (misreported)Yellow ALERT LED 3 flashes (misreported) — Compressor Short Cycling issue check
Source: Bryant Comfort Alert Diagnostic Module
Open Manual (Page 29)Search more codes in this manual