Bryant · Comfort Alert Diagnostic Module
The compressor contactor has failed in the closed position, meaning the compressor will always run when power is supplied, regardless of the thermostat demand.
Click steps to track your progress.
Turn off unit power supply and install a lockout tag.
Inspect the compressor contactor to see if it is stuck closed.
Verify the thermostat demand signal (Y) is correctly connected to the module.
Check that the 24VAC is present across Y and C when the thermostat demands operation.