5514

Warning Z1 Evap. Pressure on JR0 too low — Evaporation pressure too low

Bosch · Compress 7000 Heat Pumps

What does 5514 mean?

This warning indicates that the temperature reading from sensor JR0 is below -27°C for more than 30 seconds. This suggests issues with air flow, the fan, expansion valves, or the I/O module.

Common Causes

  • Blocked or low air flow through the air heat exchanger of the Heat Pump.
  • Defective fan or missing supply voltage/control signal to the fan.
  • One of the expansion valves is stuck in its closed position.
  • Defective I/O module.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Ensure there is sufficient and unobstructed air flow through the Heat Pump's air heat exchanger.

  2. 2

    Activate the test function for the outdoor unit to check if the fan is running and expansion valves are opening.

  3. 3

    If the warning persists, contact a qualified technician to check fan voltages, expansion valve control cables, and the I/O module.