Bosch · Compress 7000 Heat Pumps
The room sensor displays an error code (A21, A22, A23, or A24) because the EMS bus signal has gone absent from the parent controller (display HMC300/HPC400) after successful installation.
Click steps to track your progress.
Check both ends of the EMS cabling connections between the display (HMC300/HPC400) and the installer module boards.
Ensure all connections are secure and properly seated.
If the problem persists, contact a qualified installer to inspect the cabling for damage or interference.