Low Liquid Leaving Temp Fault

Low Liquid Leaving Temp Fault

York · Air-Cooled Chillers

What does Low Liquid Leaving Temp Fault mean?

The temperature of the liquid leaving the unit is lower than the setpoint, potentially causing issues or indicating a problem.

Common Causes

  • Improperly adjusted leaving chilled liquid temp. cutout (glycol only)
  • Micro panel setpoint/range values improperly programmed
  • Chilled liquid flow too low
  • Defective LWT or RWT sensor

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Re-program the leaving chilled liquid temperature cutout.

  2. 2

    Re-adjust the setpoint/range values on the micro panel.

  3. 3

    Increase chilled liquid flow, referring to installation limitations.

  4. 4

    Compare suspect sensor readings against a known good temperature device.

Browse all codes in this manual (23)
Verified technical data. Last updated: April 2026