A ground fault has been detected within the PV system. This can be identified by specific voltage measurements within the PV array, where the sum of positive to ground and negative to ground voltages approximately equals the total string voltage.
Click steps to track your progress.
Disconnect the inverter from all voltage sources using the installation manual's instructions for safety.
Measure the voltage between the positive terminal and ground (PE).
Measure the voltage between the negative terminal and ground (PE).
Measure the voltage between the positive and negative terminals.
If a ground fault is confirmed by the voltage measurements, determine its location by comparing voltage ratios and rectify the fault.
If voltages are stable but ground fault cannot be definitively located by voltage, measure insulation resistance.