Schneider Electric Micrologic Control units 2.0 A, 5.0 A, 6.0 A, 7.0 A St

19 fault codes documented

Ap LED

Auto-protection trip LED

This LED indicates the circuit breaker has tripped due to its internal auto-protection function, such as overheating or a short-circuit beyond its capacity.

Arrow press to confirm

Confirming and locking a new setting

Press the 'arrow' button to confirm and lock the new setting you have selected. The flashing stops, and a closed padlock icon appears.

Battery low indication

Battery charge low indication

The system is indicating that the control unit's battery charge is low. This may affect certain functions or data logging.

Battery test button

Battery status check

Pressing this button displays the current charge level of the internal battery, which maintains fault indications.

Fault - ZSI related

Fault detected by upstream device

An upstream device has detected a fault. Depending on the settings, this may cause a delay in tripping to allow downstream devices to clear the fault.

Fault-trip reset button

Resetting fault indications

This button is used to clear any active fault or trip indications after the cause has been identified and addressed.

Ig/I∆n LED

Ground-fault or earth-leakage trip LED

This LED indicates that the circuit breaker has tripped due to a ground-fault (Ig) or earth-leakage (I∆n) condition.

Ir LED

Long-time current setting exceeded LED

This LED indicates that the long-time current setting (Ir) has been exceeded, causing a trip.

Isd/Ii LED

Short-time or instantaneous trip LED

This LED signals a trip caused by exceeding the short-time pickup (Isd) or instantaneous pickup (Ii) settings.

Jumper missing for ZSI

Short-time and ground-fault delays are zero due to missing ZSI jumper

If the circuit breaker is equipped for ZSI protection but the protection function is not used, a jumper must be installed. Without it, the short-time and ground-fault tripping delays will be set to zero, preventing proper discrimination.

Menu + Arrow 4s hold

Accessing first screen of communication settings

Holding the 'menu' and 'arrow' buttons for four seconds allows you to access the first screen of the communication settings branch. A padlock icon indicates if the setting is locked.

Menu press to next parameter

Moving to the next parameter or branch

Press the 'arrow' button to proceed to the next parameter within the current branch. Press the 'menu' button to go to the next major settings branch (e.g., from communication to measurement settings).

Padlock icon closed

Padlock icon closed — Modbus address locked

A closed padlock icon is displayed next to the Modbus address. This means the current setting is locked and cannot be changed without unlocking it first.

Padlock icon open

Padlock icon open — Modbus address unlocked

An open padlock icon is displayed. This means the Modbus address is unlocked and ready for modification.

Quick View press to select

Selecting a new setting value

Press the 'Quick View' button to scroll through and select new values for a setting. Each press moves to the next option in a loop.

Quick View press to unlock

Unlocking a setting for modification

Pressing the 'Quick View' button after accessing a setting allows you to unlock it. The setting, or the first digit of a two-digit setting, will then flash, indicating it's ready to be changed.

Second digit flashing — Ready to change Modbus address

Second digit flashing — Ready to change Modbus address

The second digit of the Modbus address is flashing on the display. This means it is ready to be modified.

Trip history available

Trip history available for review

The control unit has recorded past tripping events. This history can be accessed for analysis and troubleshooting.

Unlock first digit, then modify

First digit flashing — Ready to change Modbus address

The first digit of the Modbus address is flashing on the display. This indicates that the unit is ready for you to change this digit.