Mitsubishi Electric · City Multi Air Conditioning Systems
This error indicates that there's a continuous failure in data transmission, meaning the system is not receiving a response 'frame' or packet. This can be caused by continuous noise, a decline in transmission voltage/signal due to line issues, or a malfunction in the error source controller.
Click steps to track your progress.
Turn off the power to the entire system at the main circuit breaker.
Check all transmission lines for proper length (max 200m / 656ft total, max 12m / 39ft for remote controller line) and correct wire type (CVVS, CPEVS, or MVVS with 1.25mm² / AWG16 or more).
Inspect for any potential sources of continuous electrical noise that might be interfering with communication.
Ensure all connectors are firmly seated.
Restore power. If the problem persists, a qualified technician should check transmission voltage and diagnose controller malfunctions.