Mitsubishi Electric · City Multi Air Conditioning Systems
This error indicates a problem with the indoor unit's gas-side pipe temperature sensor (TH23). This could be due to a faulty thermistor or a loose connection, leading to inaccurate temperature readings for the gas pipe.
Click steps to track your progress.
Turn off the power to the indoor unit at the circuit breaker.
Check the connector for the TH23 thermistor on the indoor unit to ensure it is securely connected.
Visually inspect the thermistor's lead wire for any visible damage.
Restore power to the unit. If the error persists, note the ambient temperature.
A technician would typically check the thermistor resistance at different temperatures (e.g., 0°C, 10°C, 20°C, 30°C, 40°C) against specified values (15kΩ, 9.7kΩ, 6.4kΩ, 4.3kΩ, 3.1kΩ respectively).