5102 (1217)

5102 (1217) Temperature sensor fault - Indoor unit pipe temperature (TH22)

Mitsubishi Electric · City Multi Air Conditioning Systems

What does 5102 (1217) mean?

This fault signals an issue with the indoor unit's pipe temperature sensor (TH22). A defective thermistor or a connection problem can cause this, resulting in inaccurate pipe temperature readings.

Common Causes

  • Defective thermistor (TH22).
  • Loose or poor contact of the thermistor connector.
  • Faulty indoor board if no other issues are found.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Turn off the power to the indoor unit at the circuit breaker.

  2. 2

    Check the connector for the TH22 thermistor on the indoor unit to ensure it is securely connected.

  3. 3

    Visually inspect the thermistor's lead wire for any visible damage.

  4. 4

    Restore power to the unit. If the error persists, note the ambient temperature.

  5. 5

    A technician would typically check the thermistor resistance at different temperatures (e.g., 0°C, 10°C, 20°C, 30°C, 40°C) against specified values (15kΩ, 9.7kΩ, 6.4kΩ, 4.3kΩ, 3.1kΩ respectively).

Browse all codes in this manual (51)