CodeRegistry
Brands
  1. Home
  2. Mitsubishi Electric
  3. City Multi Air Conditioning Systems
  4. 5101 (1202)
About·Privacy·Terms

CodeRegistry — Your global library for technical solutions.

For your safety: always follow the equipment manufacturer’s official manuals. CodeRegistry is an independent help site and is not affiliated with the brands listed here.

5101 (1202)

5101 (1202) Temperature sensor fault - Return air temperature (TH21)

Mitsubishi Electric · City Multi Air Conditioning Systems

What does 5101 (1202) mean?

This error indicates a problem with the return air temperature sensor (TH21) in the indoor unit. It could be due to a faulty thermistor or a bad connection, leading to incorrect temperature readings for the return air.

Common Causes

  • Defective thermistor (TH21).
  • Loose or poor contact of the thermistor connector.
  • Faulty indoor board if no other issues are found.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Turn off the power to the indoor unit at the circuit breaker.

  2. 2

    Check the connector for the TH21 thermistor on the indoor unit to ensure it is securely connected.

  3. 3

    Visually inspect the thermistor's lead wire for any visible damage.

  4. 4

    Restore power to the unit. If the error persists, note the ambient temperature.

  5. 5

    A technician would typically check the thermistor resistance at different temperatures (e.g., 0°C, 10°C, 20°C, 30°C, 40°C) against specified values (15kΩ, 9.7kΩ, 6.4kΩ, 4.3kΩ, 3.1kΩ respectively).

Browse all codes in this manual (51)
Verified technical data. Last updated: April 2026

Related Faults

0403 (Ed)0403 (Ed) Serial communication error1102 <1202> (U2)1102 <1202> (U2) Compressor temperature trouble1302 <1402> (UE)1302 <1402> (UE) High pressure trouble
Source: Mitsubishi Electric City Multi Air Conditioning Systems
Open Manual (Page 4)Search more codes in this manual