Alarm 137

Alarm 137 — Low Outdoor Airflow

Lennox · PRODIGY 2.0 Unit Controller

What does Alarm 137 mean?

This alarm is triggered when the actual outdoor air intake is less than the target outdoor air by a specified percentage (set by Parameter 239) for a prolonged period (set by Parameter 243).

Common Causes

  • Outdoor air damper is not opening sufficiently.
  • Obstruction in the outdoor air intake.
  • Malfunctioning outdoor air sensor.
  • Incorrect settings for Parameter 239 or 243.
  • Reduced supply airflow demand.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Inspect the outdoor air intake for obstructions.

  2. 2

    Verify the operation of the outdoor air damper.

  3. 3

    Check the outdoor air sensor for accuracy.

  4. 4

    Review the settings for Parameter 239 (Advanced Airflow Outdoor CFM Alarm Set Point) and Parameter 243 (duration).

  5. 5

    Ensure the system is correctly configured for outdoor air intake.

Browse all codes in this manual (56)
Verified technical data. Last updated: April 2026