F3

F3 — Compressor discharge temperature sensor error

Lennox · Air Conditioning

What does F3 mean?

This error indicates a malfunction with the compressor discharge temperature sensor (T5). This sensor monitors the temperature at the compressor's outlet.

Common Causes

  • Faulty compressor discharge temperature sensor (T5)
  • Open circuit or short circuit in the sensor wiring
  • Loose connection to the main control board

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Check the connections of the compressor discharge temperature sensor (T5) to the outdoor unit main control board.

  2. 2

    Inspect the sensor wiring for any open circuits or short circuits.

  3. 3

    Check the resistance value of the compressor discharge temperature sensor against the specifications in the manual.

  4. 4

    If the sensor resistance is abnormal, replace the sensor.

  5. 5

    If the sensor and wiring are fine, consider replacing the outdoor main control board.