[8] Discharge temperature too high protection

Error 8 — Compressor discharge temperature too high

Haier · Air Conditioning

What does [8] Discharge temperature too high protection mean?

The compressor discharge temperature has exceeded 115°C. The error will clear within 3 minutes if the temperature drops below this threshold. If it happens 3 times in an hour, the system will lock.

Common Causes

  • The sensor is bad or improperly fixed
  • The system is clogged
  • The system lacks refrigerant
  • Incorrect valve opening

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Check if the sensor wiring is firmly in place.

  2. 2

    Measure the sensor resistance to see if it is within range.

  3. 3

    Check if the system is clogged.

  4. 4

    Check if the PMV coil wiring is okay.

  5. 5

    Ensure the stop valve is open.

  6. 6

    Check if the system is low on refrigerant.