The low pressure switch circuit has been detected as open for 60 seconds after the compressor has been running for 3 minutes, or open for 30 seconds while the system is in standby.
Click steps to track your progress.
Check if the pressure switch wiring connection is okay.
Use a multimeter to check if the high pressure switch terminal is short-circuited.
Ensure the Electronic Expansion Valve (EEV) coil is fully seated.
Check if the service valve is open.
Short the high pressure switch terminal on the PCB to see if the system reports a failure.
Check if the piping system is clogged.