Grundfos · MAGNA3 Circulator Pumps
The pump is receiving a signal from an external sensor that falls outside its normal operating range. This is a warning and does not activate the alarm relay.
Click steps to track your progress.
Verify that the electrical signal setting for the analog input on the pump matches the output signal of the external sensor (e.g., 0-10V or 4-20mA). Adjust settings if necessary (see section 8.6.7 'Analog Input', page 32).
Check the external sensor cable for any visible damage along its length.
Inspect the cable connections at both the pump and the external sensor to ensure they are secure and correct.
If the external sensor has been removed, ensure the analog input function has been disabled in the pump's settings.
If the warning persists after these checks, contact Grundfos Service; the sensor may need replacement.