Fujitsu · Air to Water Heat Pumps
The hydraulic unit's green LED flashes nine times and the red LED flashes four times, or the outdoor unit LED flashes 13 times. This signifies that the system has detected an excessive electrical current, leading to a protective shutdown.
Click steps to track your progress.
First, turn off the power to the heat pump system at the main breaker for 60 seconds, then restart it.
Check all terminal connections in the control unit for any looseness, disconnected wires, or incorrect wiring; correct as needed.
Inspect the outdoor heat exchanger for any obstructions, dirt, or debris blocking airflow and clean it thoroughly if clogged.
Check the outdoor fan motor for proper operation (ensure it spins freely) and replace if faulty (refer to 'Clear 18' for fan motor issues if applicable).
If the above checks don't resolve the issue, contact a qualified technician as it may indicate a compressor or inverter PCB failure.