C2 Locked Out Due to High Pressure

Refrigeration Circuit 2 High Pressure Lockout

York · Smart Equipment Control

¿Qué significa C2 Locked Out Due to High Pressure ?

This alarm occurs when 24 VAC power is lost from the HPS2 terminal, indicating a high-pressure condition in refrigeration circuit 2. Multiple occurrences within an hour will cause a hard lockout.

Causas comunes

  • High pressure switch activated
  • Dirty or blocked condenser coil
  • Condenser fan or low ambient control not working
  • Improper SEC board configuration
  • System overcharged
  • Blocked liquid line filter
  • Faulty TXV (Thermostatic Expansion Valve)
  • Loose wire connection on the high pressure switch

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Connect pressure gauges and check suction and discharge pressures for refrigeration circuit 2.

  2. 2

    Clean or clear any blockages in the condenser coil.

  3. 3

    Verify the condenser fan and low ambient control are functioning correctly.

  4. 4

    If a split system, check that solenoid valves are energized and opening.

  5. 5

    Ensure the SEC board is properly configured.

  6. 6

    Check system charge, liquid line filter, and TXV operation.