Nibe · Ground Source Heat Pumps
This alarm indicates that the voltage for compressor 2 has been below 160 V for 30 minutes. This can cause the compressor to block.
Haga clic en los pasos para seguir su progreso.
Check the electrical supply for phase failures.
Verify fuses are intact.
Inspect the soft start card for defects.