This fault is related to the liquid pipe thermistor (TH2), indicating it may be disconnected, have an open circuit, or a short circuit.
Haga clic en los pasos para seguir su progreso.
Ensure the TH2 thermistor is properly connected.
Examine the wiring connected to TH2 for damage or loose connections.
Measure the resistance of the TH2 thermistor (consult manual for values).
Replace the TH2 thermistor if found to be defective.