F2

F2 — Outdoor coil temperature sensor error

Lennox · Air Conditioning

¿Qué significa F2 ?

The system has detected an issue with the outdoor coil temperature sensor (T3). This sensor helps regulate the unit's performance based on outdoor conditions.

Causas comunes

  • Faulty outdoor coil temperature sensor (T3)
  • Loose connection between the sensor and the main control board

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Verify that the connections between the outdoor coil temperature sensor and the outdoor unit main control board are secure.

  2. 2

    Check the resistance value of the outdoor coil temperature sensor against the specifications in the manual.

  3. 3

    If the sensor resistance is not within the normal range, replace the sensor.

  4. 4

    If the sensor resistance is normal, replace the outdoor main control board.